Bewator Ltd. 5PQ5290 User Manual

Page of 2
IN062 - Issue 1A October 1999 - Page 1 of 2
5298 PIN & Proximity Reader
IN062
Mounting, connecting and setting up
Mount the 5298 Reader in a suitable position near the door approximately 1.2m
from the floor.
The Reader has a mounting plate with two mounting holes which are suitable for
most installations.
1.
If the Reader is fixed to the mounting plate, undo the two screws which are
at the top right and bottom left of the keypad, then place the mounting plate
in position on the wall or door frame and mark the position of the two
mounting holes - these are the two oval holes in the mounting plate.
2.
Drill the two mounting holes. The holes accept 3.5mm machine screws or
No 6 wood screws.
3.
The connections are made to CONN1 on the rear of the Reader. Pass the
cable through the large hole in the centre of the mounting plate and make
the connections shown in the following table as required.
CONN1
Name
Function
1
V+
Power supply +V (+ve)
*(see below for voltage range in each jumper setting)
2
0V
Power supply 0V (-ve),
(also ground reference for data output)
3
H
Data Hold for Wiegand output (+5V max)
4
Horn
Horn - 0V to sound, +5V to turn off
5
R
Red LED control - 0V for red LED
6
R/G
Single wire LED control
0V for green LED, +5V for red LED
(red and green LEDs on together give amber)
7
D0
Data zero for Wiegand output
8
D1
Data one for Wiegand output
9
DA
Data Available for Wiegand output
*
Jumper JU1 on the circuit board determines the range of voltage which can
be used to power the Reader as shown in the following table.
JU1
Power supply voltage range
24
unregulated DC: max 35.0V*, min 15.6V, 100mA max
5/15
unregulated DC: max 15.6V, min 4.0V, 100mA max
*
If you are using a power supply at or near the 35V maximum, the ambient
temperature of the environment where the Reader is installed must not
exceed 55
o
C.