Digital Security Controls Ltd. 00LINKS2450 User Manual

Page of 12
1
INTRODUCTION
Section 1
The LINKS2450 transmits alarm system information over a long-range radio
network. It may be used with the following DSC alarm control panels:
• PC1575/1580 v1.0
• PC4010/4020 v3.x
• PC1555/1565 v2.x and up
• PC5015 v2.2
• PC580/585 v2.x
• PC5010 v1.0 and up
This manual will describe how to install and program the LINKS2450 for connection
to the above panels.
1.1 Specifications
NOTE: If the panel uses automatic SIA or Contact ID communications formats, the
reporting codes the LINKS2450 will send must still be programmed on the panel.
• Power supply: 11.5-14V
DC
 at 750mA (PS1520, PC5204, PC4204, or powered
from Bell+/Aux- control panel terminals)
• Radio transmitter frequency: range from 440 to 470MHz
• Communication Buffer: 80 Events
• Transmission Range:  Approximately 16 Kilometers (10 Miles)
• Cabinet dimensions: 4.17” high × 5.75” wide × 1” deep (104mm × 146mm ×
26mm); color: white
• Module supervision via the alarm control panel
• Protected against static and lightning induced transients
• Programming by keypad or downloading software. The LINKS2450 is complete
with a default program and is operational with a minimum of programming.
• To program via a keypad when connected to PC5015, PC5010, PC1575/1580,
PC1555/1565 or PC580/585 panels, program the LINKS2450 using any
system keypad
• To program via a keypad when connected to PC4010/4020 v3.0 panels,
program the LINKS2450 using a PC2550RK keypad connected directly to the
LINKS2450.
• EEPROM Memory
The LINKS2450 uses EEPROM memory, which will retain all program
information even if AC and battery power, are removed.