Digital Security Controls Ltd. 00NB9001 User Manual

Page of 34
3
S e c t i o n   2 :   C o m p l e t i n g   W i r i n g
This section describes special options for AC or battery power, and instructions on installing hardwired zones and the remote sounder.
2.1
AC and Battery Hookups
AC Terminals - AC
Connect the AC and telephone line wiring to the terminals 
mounted on the NT9010 backplate. When you later attach the 
NT9010 to the backplate, the posts on the back of the unit will 
plug into the terminals, completing the connection.
For the NT9010 to work correctly, 
you will need to connect it to an 
AC power source that is not con-
trolled by a switch. The system 
comes with a 9V, 20VA plug-in 
transformer. Connect the trans-
former to an unswitched AC source and to the two terminals on 
the backplate labelled AC.
The system can be programmed to accept a power line frequency 
of either 50Hz AC or 60Hz AC in programming section [701], 
option [1].
NOTE:
Do not connect the transformer until all other wiring 
is complete.
AC Power Line Frequency  . . . . . . . . .  Section [701], Option [1]
Battery Connection
The battery is used to provide back up power in the event of an 
AC power failure and to provide additional current when the sys-
tem demands exceed the power output of the transformer, such 
as when the system is in alarm.
NOTE:
Do not connect the battery until all other wiring is 
complete
.
Connect the RED battery lead to the positive of the battery, the 
BLACK battery lead to the negative.
The High Current Charge/Standard Battery Charge option 
(section [701], option [7]) allows you to choose between a high 
current battery charge and the standard battery charge rate.
High Current/Standard Battery Charge Section [701], Option [7]
2.2
Telephone Connection Terminals - TIP, 
RING, T-1, R-1
If a telephone line is 
required for central station 
communication or for 
downloading, connect an 
RJ-31X jack to the R-1, T-1, 
RING, and TIP terminals on 
the backplate as shown 
below.
NOTE:
 
Please ensure that all 
plugs and jacks meet the 
dimension, tolerance and 
metallic plating require-
ments of 47 C.F.R. Part 68, 
SubPart F.
 
For proper operation there must be no other 
telephone equipment connected between the control 
panel and the telephone company facilities.
Do not connect the alarm system communicator to tele-
phone lines intended for use with a FAX machine. These 
lines may incorporate a voice filter which disconnects the 
line if anything other than FAX signals are detected, result-
ing in incomplete transmissions
.
2.3
Zone Wiring
You can connect up to two hardwired zones to the NT9010. For 
the hardwired zones to work correctly, you must enroll them with 
the system (see section 5.3 “Enrolling Hardwired Zones” on 
page 16). For a complete description of the operation of all zone 
types, please see section 5.1 “Zone Definitions” on page 15. 
Use the following NT9010 terminals to 
make your zone connections:
There are two different ways in which 
zones may be wired, depending on 
which programming options have been 
selected. The system can be programmed 
to supervise normally closed, or Single 
End of Line loops. Please refer to the following sections to study 
each type of individually supervised zone wiring. 
Normally Closed (NC) Loops
To enable normally closed loops, programming section [013], 
option [1] must be ON.
NOTE:
 This option should only be selected if Normally 
Closed (NC) devices/contacts are being used.