C h a p t e r   2 :   A d v a n c e d   P r o g r a m m i n g
4 0
2.3.5
Wireless 
Zone 
Supervision
NOTE:
 The RF Jam Detect zone, hardwired zones, and Panic Pendants 
must have the supervision option disabled.
Wireless Supervisory Window
Each wireless zone will send a supervisory signal every 64 minutes. If the receiver 
does not receive a signal within the time programmed for the Wireless Supervi-
sory Window
, it will generate a supervisory fault. 
To program the wireless supervisory window, from Advanced Programming:
1. Enter section [804].
2. Enter sub-section [81]. 
3. Enter the time period for the supervisory window (valid entries are 01-24 hours).
4. To exit press [#].
Disable/Enable Zone Supervision
When you enroll a zone through the NT9010 Flash Programming, the Wizard will 
automatically turn on supervision for the zone. To disable supervision for any zone, 
enter the following through Advanced Programming:
1. Enter section [804].
2. Enter sub-section [82], [83], [84] or [85]. Disable or enable supervision for each 
wireless zone by turning each relevant option on or off.
3. To exit press [#].
NOTE:
 If you replace an RF Jam Detect zone or hardwired zone with a 
different type of device (e.g. a motion detector), supervision of the device 
will not be turned on automatically. You must turn it on as described above.
2.3.6
RF Jamming 
Detection 
Zone
For RF jamming detection to work, you must select an unused zone to be used as 
the RF Jam Detect zone. When the NT9010 system detects an attempt to jam the 
RF signal, the RF Jam Detect zone will be violated and the system will generate a 
tamper signal. When the jamming signal is gone, the RF Jamming Detection zone 
closes and the system sends a tamper restore signal. 
To enable RF jamming detection, from Advanced Programming:
1. Enter programming section [807], then sub-section [093].
2. Select an unused zone to be the RF Jam Detect zone. Enter the 2-digit number 
([01] to [32]) of the RF Jam Detect zone on the keypad.
3. Program a Zone Definition for the zone number you assigned to the RF Jam 
Detect zone. A 24-hour zone type is recommended if this is used.
4. RF jamming detection is now enabled. To exit Advanced Programming, press 
[#].
NOTE:
 If you need to change the RF Jamming Detection Zone, you 
should first delete the zone by entering (00) in section [807], sub-section 
[093].
NOTE:
Programming RF Jam Zone will automatically program the corre-
sponding label as RF Jam. Please be sure that the corresponding serial num-
ber is (000000). RF Jam will not work properly otherwise