Digital Security Controls Ltd. 01NB9010 User Manual

Page of 68
S ec ti o n   2 . 3 :   C h a n g i n g   O t h e r  N T 9 0 10   F u n c t i o n s
4 7
Pager Format
The Communicator Format option for either telephone number can be pro-
grammed for Pager Format. If an event occurs and the Communicator Call Direc-
tion 
options direct the call to a telephone number with the Pager Format selected 
the system will attempt to page.
When calling a pager extra digits will be required to make it work properly.
The following is a list of Hex digits and what function they perform:
HEX (B) - simulates the [✱] key on a Touch Tone telephone
HEX (C) - simulates the [#] key on a Touch Tone telephone, or
end of telephone number marker
HEX (D) - forces the system to search for dial tone
HEX (E)
- forces the system to pause for 2 seconds
HEX (F)
- end of telephone number marker
The system will attempt to call the pager one time. After dialing the digits in the 
telephone number the system will send the account number and reporting code 
followed by the [#] key (Hex [C]).
There is no ringback when using Pager Format. The system has no way of confirm-
ing if the pager was called successfully. A failure to communicate trouble will only 
be generated once the maximum number of attempts has been reached.
NOTE:
 Do not use the digit C in a reporting code when using Pager For-
mat. In most cases, the digit C will be interpreted as a [#], which will termi-
nate the page before it has finished.
NOTE:
 If the system detects a busy signal, it will attempt to page again. 
It will make the maximum number of attempts programmed in section 
[160]. 
NOTE:
Force dialing should be disabled when using Pager format.
NOTE:
 When using Pager format, you must program two pauses (hex 
digit E) at the end of the telephone number.
Communicator Format Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [360]
2.3.12 CommunicatorR
eporting 
Codes
Unless you are using Automatic Contact ID or Automatic SIA formats, reporting 
codes must be programmed in order for the system to report events to the central 
station.
Reporting codes are two digits and can use hexadecimal digits A through F. To disable 
a reporting code, program it as “FF” (default setting) or “00”. For a complete 
description of reporting codes which can be programmed and lists of automatic Con-
tact ID and SIA format codes, please see Appendix B: Reporting Codes on page 
58.
Transmission Delay
The Transmission Delay feature is used to delay reporting of alarms. When a zone is 
violated and causes an alarm, the Transmission Delay Timer will start. When the