Digital Security Controls Ltd. 143G4010 User Manual

Page of 24
3G4010 Wiring Diagrams
13
 Figure 2 - Wiring Diagram
5
4
1
2
36
789
10
11
14
15
16
17
LE
LI
O1
O2
O3
O4
+OC
13
12
AS
L1
L2
L3
L4
1K5
This
Connection
is
necessary
T I P
T I P
R I N G
R I N G
3G4010
3
2
DC IN
AUX
23
1
COM
4
1
COM
T1
R1
TIP
RING
4
PGM
ZONE
+
-
RJ-45
BA
TTER
Y
Sealed Rechargeable
12V / 1.2Ah
Typical batter
y charge: 30-50 mA
Recommended Model: 12V/1.2Ah or 
12V/7Ah (for order code 3G4010 only) 
Batter
y not required
if CON5 is ON
9-14V
DC
/ *700mA (max)
Earth-ground
Ground wire from building electrical installation
Inputs to be connected
to dr
y contact outputs
from alarm control panel
with 5.6K
Ω 
EOL resistors
}
GROUND CONNECTION
Tighten nut to break paint & make good connection to  the cabinet.
Nut
Nut
Bolt
Lock washer
Lock washer
Star washer
Cabinet
Alarm Control P
anel with
Dialler Interface
(Supports Contact ID format)
Panel Aux P
ower
or External P
ower
Supply (13.8V
DC 
required for normal, long-term operation)
Telephone Line
Connection
Super
vision
Relay
RM1-UL Installations RM1C-ULC Installations
W
ARNING:
 Incorrect connections may result in PT
C failure or improper operation. Inspect wiring and ensure connections are correct befor
e turning on.
Connect relay contacts to a zone input on the alarm control panel for 3G4010
troubles super
vision 
(24hr
-type zone)
Optional
use of PGM
output (See
Programming)
W
ARNING!
HIGH VOL
TAGE. DISCONNECT AC
POWER & TELEPHONE LINES
PRIOR TO SERVICING
All circuits are classified for UL installations as P
ower Limited/Class II P
ower Limited except for the batter
y leads which are
 not P
ower Limited. Do not route any wiring 
over circuit boards. Maintain at least 1” (25.4mm) separation. A minimum 1/4” (6.4mm) separation must be maintained at all poin
ts between P
ower Limited wiring 
and all other Non-P
ower Limited wiring.  Route wires as indicated in the diagram.
NOTE: For ULC Commercial Fire and Burglar
y Installation requirements please refer to Figures 5, 6, 7 & 8 and to the ULC Install
ation Guide P/N 29002157R009.
 
(Use No. 26 A
WG wires for
the  connection to PSTN)
*Refer to Jumper 3 section     for current rating
For ULC Fire Monitoring installations fire alarm signals shall be sent 
simultaneously over POTS line (using the dialler) and over the wireless 
network (using 3G4010). Connect alarm output from control panel (PGM) 
to the input on the 3G4010 that is programmed as a Fire Alarm Input.
Examples of Control Units/Subscribers Units or P
ower Supplies compatible
models:  DSC PC1864, PC1832, PC1616, PC5204, etc.