3G4010 Wiring Diagrams
16
 Figure 7 - DSC Subscribers’ Unit Fire and 3G Wireless Transmitter Mounted Remotely
Alternate Wiring Diagram for DSC Subscribers’ Unit Fire and wireless Transmitter
Passive Communication System -Using Phone Line Supervision Relay 
PLEASE NOTE THAT EITHER RM1C ULC OR RM2 RELAYS
CAN BE USED FOR ULC INSTALLATIONS
 
 
 
 
 
 
 
 
 
 
 
 
         
Fire Alarm 
Control Unit 
Outputs 
Fire
Supervisory 
Trouble 
DSC
Subscribers’ 
Unit Fire
Zone
Inputs
TIP
RING
                 PGM1  
DSC Keypad 
LCD4501 
PK55XX
3G Wireless
Transmitter 
3G4010
T1/R1     
PGM1     
           TIP/RING 
Zone         
Input         PGM4 
AUX Power 
12V/700mA 
RM1C ULC 
Relay 
PC5003C
PC4050CR
cabinet
3G (HSPA)/2G (GPRS)
 
PSTN
AC Input 
AC Input 
PC4020 
PC1864 
PC1832 
PC1616
RM1C ULC 
Relay 
GS30XX cabinet 
RM1C ULC 
Relay 
NOTES:  
- Connect PGM output from 3G4010 (Phone Line Trouble) 
to a zone input on the subscriber unit for supervision of the 
phone line voltage.
- When the 3G4010 is installed remotely from the DSC 
Control Panel, it is required to monitor the Phone Line 
Trouble condition at the keypad by using an additional 
RM1C Relay. 
- Refer to detailed diagrams in Figure 8.