Chapter 11.0 Locating Detectors and Escape Plan
11.0 Locating Detectors and Escape Plan
The following information is for general guidance only and it is recommended that local fire codes 
and regulations be consulted when locating and installing smoke and CO alarms.
11.1 Smoke Detectors
Research has shown that all hostile fires in homes generate smoke to a greater or lesser extent. 
Experiments with typical fires in homes indicate that detectable quantities of smoke precede detect-
able levels of heat in most cases. For these reasons, smoke alarms should be installed outside of 
each sleeping area and on each storey of the home.
The following information is for general guidance only and it is recommended that local fire codes 
and regulations be consulted when locating and installing smoke alarms.
It is recommended that additional smoke alarms beyond those required for minimum protection be 
installed. Additional areas that should be protected include: the basement; bedrooms, especially 
where smokers sleep; dining rooms; furnace and utility rooms; and any hallways not protected by 
the required units. On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. 
Other spacing may be required depending on ceiling height, air movement, the presence of joists, 
uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-02 or other 
appropriate national standards for installation recommendations.
 
l
Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in 
these locations may prevent the unit from detecting smoke.
 
l
Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air move-
ment around the detector may prevent smoke from entering the unit.
 
l
Do not locate detectors in areas of high humidity.
 
l
Do not locate detectors in areas where the temperature rises above 38ºC (100ºF) or falls 
below 5ºC (41ºF).
 
l
Smoke detectors must always be installed  in USA in accordance with Chapter 29 of 
NFPA 72, the National Fire Alarm Code: 29.5.1.1.
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved 
single- and multiple-station smoke alarms shall be installed as follows:
1. 
In all sleeping rooms and guest rooms.
2.
Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any door to a 
sleeping room, the distance measured along a path of travel.
3.
On every level of a dwelling unit, including basements.
4.
On every level of a residential board and care occupancy (small facility), including basements 
and excluding crawl spaces and unfinished attics.
5.
In the living area(s) of a guest suite.
6.
In the living area(s) of a residential board and care occupancy (small facility).
Figure 1
Figure 2
Figure 3