Digital Monitoring Products Inc PC0128 User Manual

Page of 31
Digital Monitoring Products
 
XT30/XT50 Installation Guide
12
InstallatIon
10.3  Zone Response Time
A condition must be present on a zone for 500 milliseconds before it is detected by the panel. Ensure
detection devices used on the protec tion zones are rated for use with this delay.
10.4  Keyswitch Arming Zone
You can use a momentary keyswitch on a zone programmed as an Arming type for use in arming and
disarming the system without a code.
Powered Zone for 2-Wire Smoke Detectors
11.1  Terminals 25 and 26
A resettable 2-wire Class B powered zone is provided on terminals 25 (positive) and 26 (negative) of the
panel. For programming purposes, the zone number is 10 on the XT30/XT50. The zone uses a Model 309, 3.3k
Ohm EOL resistor (provided with the panel) and has an operating range of 8.8 to 13.9 VDC.
The compatibility identifier is: B
Caution: Sensor reset on zone 10 drops power to devices on this zone, causing the panel to sense an open
condition on all zone types other than Fire, Fire Verify, and Supervisory. Whenever non-Fire and non-
Supervisory zone types are used on zone 10, make the appropriate adjustments to the zone’s Armed Action
to prevent false alarms from occurring.
Manufacturer
Model
Detector 
ID
# of 
Detectors
Zone Expansion Modules
DMP/Hochiki
SLR-835B
HD-6
7
715, 715-8, 715-16, 725
Sentrol/ESL
429AT, 521B, 521BXT
S09A
12
715, 715-8, 715-16
System Sensor
2WTA-B, 2WTR-B
A
10
715, 715-8, 715-16
Annunciator Outputs
12.1 Description
The four annunciator outputs can be programmed to indicate the activity of the panel’s zones or conditions
occurring on the system. Annunciator outputs do not provide a voltage but instead switch-to-ground voltage 
from another source. The outputs can respond to any of the conditions listed below:
1)  Activation by zone condition: Steady, Pulse, Momentary, or Follower
6)  Ambush alarm
2)  Manually from the keypad
7)  Exit and Entry timers
3)  Communication failure
8)  System Ready
4)  Armed area annunciation
9)  Late to Close
5)  Fire Alarm or Fire Trouble
12.2  Harness Wiring
The open collector outputs are accessible by installing the DMP 300 Harness on the 4-pin header labeled J11.
The output locations are shown below. For listed applications, devices connected to outputs must be located 
within the same room as the panel.
 
Output   Color    Wire 
Output   Color    Wire
1
Red
1
3
Green  3
2
Yellow
2
4
Black
4
12.3  Model 860 Relay Module
Connect a Model 860 Relay Module to the panel to provide relays for the annunciator outputs that can be
used for electrical isolation between the alarm panel and other systems or for switching voltage to control 
various functions. The module includes one relay and provides three additional sockets for expansion of up
to four relays. Power is supplied to the relay coils from the panel keypad bus. The 860 mounts inside the
panel enclosure using the 3-hole mounting configuration. Plastic standoffs are provided with the module for
ease of installation. A 4-wire harness is also provided that connects the Model 860 to the panel.
Relay Contact Rating:  1 Amp at 30 VDC