Digital Monitoring Products Inc PC0128 User Manual

Page of 31
XT30/XT50 Installation Guide 
Digital Monitoring Products
1
Panel sPecifications
Panel Specifications
1.1  Power Supply
Transformer Input:
Plug-in — 16.5 VAC 40 VA, Model 321
Wire-in — 16.5 VAC 40 VA, Model 320
Standby Battery:
12 VDC, 1.0 Amps Max. charging current 
Models 364, 365, 366, 368, or 369 
Replace every 3 to 5 years
Auxiliary Output:
12 VDC at 500mA
12 VDC at 325mA when used with two Model 364 batteries in the Model 341 enclosure
Bell Output:  
12 VDC at 1.5 Amps
Smoke Detector Output:
12 VDC at 100mA
All circuits inherent power limited
Note: Please see the Listed Compliance Specifications section for certificated application requirements.
1.2 Communication
Built-in SDLC Digital Dialer communication to DMP Model SCS-1R Receivers
Built-in network communication to DMP Model SCS-1R or SCS-VR Receivers
Built-in or modular cellular communication to DMP Model SCS-1R or SCS-VR Receivers
Built-in CID (Contact ID) dialer communication to DMP Model SCS-1R Receivers
1.3  Panel Zones
Nine 1k Ohm EOL burglary zones: zones 1 to 9
One 3.3k Ohm EOL Class B powered fire zone with reset capability: zone 10
1.4 Keypads/Expansion
Connect up to eight supervised alphanumeric keypads.
Connect up to four alphanumeric 9000 Series wireless keypads.
Eight keypads total per panel.
Connect additional unsupervised keypads.
•  Graphic Touchscreen, Thinline™, Aqualite™, Clear Touch™, and Icon keypads
In addition, the following zone expanders can be added:
•  One, four, eight and 16-zone expansion modules
•  Single-zone PIR and glassbreak detectors
1.5  Number of Zones
•  Onboard zones 1-10
•  Eight keypad bus addresses with zones 11-14, 21-24, 31-34, 41-44, 51-54, 61-64, 71-74, and 81-84
•  Zone numbers 31 to 34 and 41 to 44 can support 1100 Series Key Fobs or DMP wireless output modules
•  XT50 has 20 additional onboard wireless zones numbered 80-99
1.6 Outputs
The XT30/XT50 panels provide four open collector outputs rated for 50mA each. A Model 300 Output Harness
is required. The open collector outputs provide the ground connection for a positive voltage source.
1.7  Enclosure Specifications
The XT30/XT50 panel ships standard in a 340 enclosure with EOL resistors, battery leads, user’s guide, and
programming sheet.
Enclosure Model
Size
Color
Construction (Cold Rolled Steel)
340
12.5” W x 9.5” H x 2.75” D
Gray (G)
20-Gauge
349
12.5” W x 11.5” H x 3.5” D
Gray (G)
20-Gauge
349A
13.25” W x 11.65” H x 3.6” D
Gray (G)
18-Gauge with 16-Gauge door
341
13” W x 6.55” H x 3.5” D
Gray (G)
20-Gauge