Digital Monitoring Products
4
 
Version Display
 
When you connect the keypad to the 734W module, the version number and release    
 
date display.
•  Press keys 1, 2, 3, or 4 then the CMD key to show zone status of that zone. 
•  Press CMD key to enter the Diagnostic Menu.
•  Press 6653 (PROG) then CMD to enter the Programming Menu. 
 
Zone Status Display
 
The status of the entered zone number displays. To display another zone, enter the    
 
zone number followed by the CMD key. 
 
Diagnostic Menu
 
Select YES to display the Panel Communication Connect Status display.  Select NO to    
 
return to Version Display.
 
Connect Status
 
To display the connection status of the 734W to the panel, select any top row key.
 
Not Connected: The 734W cannot connect to the panel on the WiFi network.
 
Bad Passphrase: The passphrase programmed in the 734W device does not match the  
 
 
passphrase programmed in the panel.
 
Device Not Programmed: The device number programmed in the 734W is not programmed as a  
 
Device Number in the panel.
 
Duplicate Device: There is another device on the WiFi network with the same device number.
 
Transmit Time XXX: The speed in milliseconds in which the last message was sent and received  
 
between the 734W and the panel.
 
Programming Menu
 
Press the CMD key to enter programming and display initialization options.
 
 
Initialization Options
 
 
These options can set the 734W module programming memory back to factory defaults    
 
 
in preparation for programming. Press any select key to enter the initialization menu. 
 
Initialization Communications
 
Select YES to initialize the communication options back to factory defaults.  Select NO to  
 
leave communication options unchanged.
Initialize Confirm Option
 
After selecting YES to clear the Communication settings, the 734W displays SURE?  YES  NO  
 
for confirmation to clear the memory.  This is a safeguard against accidentally erasing the  
 
programming.  No memory is cleared from the programming until you answer YES to the  
 
SURE? option.  Selecting NO leaves communication options unchanged.
 
Initialization Access
 
Select YES to initialize the Access Options back to factory defaults.  Select NO to return to  
 
the INITIALIZATION menu.
    INITIALIZATION 
SURE?           YES  NO
Initialize Confirm Option
 
After selecting YES to clear the Access Options, the 734W displays SURE?  YES  NO for  
 
 
confirmation to clear the memory.  This is a safeguard against accidentally erasing the  
 
 
programming.  No memory is cleared from the programming until you answer YES to the SURE?  
 
option.  Selecting NO leaves communication options unchanged.
734W   
COMMUNICATION
 
Communication Menu
 
Press any select key to enter the Communication menu. Press the CMD key to advance to  
 
the Access Options menu. Press the back arrow to display the 734W Initialization menu.
    INITIALIZATION
ACCESS?      NO   YES
734W
VER  vvv  mm/dd/yy
 734W DOOR
 ZONE: 2   -OPEN
 
734W REX
 ZONE: 3   -SHORT
 CONNECT  STATUS
 NOT  CONNECTED
 CONNECT  STATUS
 BAD  PASSPHRASE
 CONNECT  STATUS
 DEVICE NOT PROG
 CONNECT  STATUS
 XMIT TIME xxx mS
MENU?        NO  YES
 CONNECT  STATUS
 DUPLICATE DEVICE 
 734W
 ZONE: 1   -OKAY
  CONNECT  STATUS
    INITIALIZATION
  COMMS?    NO   YES
  
734W    
INITIALIZATION   
734W
PROGRAMMER
INITIALIZATION 
SURE?           YES  NO