Digital Monitoring Products Inc PC0136 User Manual
734W Installation Guide
Digital Monitoring Products
7
SITE CODE
LENGTH: 8
Site Code Length
Enter the number of Site Code bits used. Press any Select Key to enter a number between
1-16. Default is 8. Press the COMMAND key to save the entry.
USER CODE
POSITION: 9
User Code Position
Define the User Code start bit position. Press any Select Key to enter a number between
0-255. Default is 9. Press the COMMAND key to save the entry.
USER CODE
LENGTH: 16
User Code Length
Define the total number of User Code bits used. Press any Select Key to enter a number
between 1-255. The default is 16.
REQUIRE SITE
CODE: NO YES
Require Site Code
Press the top row Select key under YES to use a site code and press the COMMAND key to
view the site code entry display. In addition to User Code verification, door access is only
granted when any one site code programmed at the SITE CODE ENTRY option matches the
site code received in the Wiegand string.
Site Code Display
You can program up to eight five-digit site codes. Site code range is 1-65535.
SITE CODE 1 displays first. Any previously programmed site code displays. Default is 127.
To change the site code, press a select key, then enter the new code. Press the COMMAND
key to save and to display the next site code.
Site Codes 2-8 default to blank.
NO. OF USER CODE
DIGITS: 5
Number of User Code Digits
The 734W module recognizes user codes from one to ten digits in length. Press any top row
Select key to enter a user code digit length between 1-10 digits. This number must match the
user code number length being programmed in the panel. Default is 5.
All bits are read and converted into a decimal number string. The number string is left
padded with '0' if needed for long user code lengths. When selecting '4' the right digit is
dropped and the next four sent.
Example: # decoded
1234567
10
digits 0001234567
5
digits
34567
4
digits
3456
No Communication with Panel
This option defines the relay action when communication with the panel has not occurred
for five seconds. Default is OFF. Press any top row Select key to change the default relay
action.
Choose the action required when the 734W cannot establish communication with the panel:
Press the first Select key to choose
OFF (Relay Always Off) — The relay does not turn on
when any Wiegand string is received.
OFF does not affect any REX operation. If
communication is lost during a door strike, relay remains on for the door strike duration,
but turns off at the end of the door strike timer.
Press the second Select key to choose
SITE (Accept Site Code) — Door access is granted
when the Wiegand site code string received matches any site code programmed at SITE
CODE 1-8. For details refer back to the REQUIRE SITE CODE option.
Press the third Select key to choose
ANY (Any Wiegand Read) — Door access is granted when
any Wiegand string is received.
Press the fourth Select key to choose
ON (Relay Always On) — The relay is always on.
Press the COMMAND key to display the next action.
Press the first Select key to choose
LAST (Keep Last State) — The relay remains in the same
state and does not change when communication is lost. If communication is lost during a
door strike, the relay remains on for the door strike duration, but then returns to it's last
state prior to doing the door strike.
734W
STOP
Stop
Press any select key to start the stop routine. When programming in complete, the Version
displays and the keypad can now be removed.
FCC Information
Electronic Emission
This device complies with CFR47 Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
(2) this device must accept any interference received, including interference that may cause undesired operation.
NO COMM WITH PNL
OFF SITE ANY ON
SITE CODE 1:
(1 - 65,535) 127
SITE CODE 2:
SITE CODE 2:
(1 - 65,535) -
SITE CODE 8:
SITE CODE 8:
(1 - 65,535) -
NO COMM WITH PNL
LAST