Honeywell International Inc. 8DL5800CO User Manual

Page of 4
 
 
 
5800CO Carbon Monoxide Detector
with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
 
GENERAL INFORMATION  
The 5800CO is a 3V battery powered wireless Carbon Monoxide 
(CO) detector intended for use with wireless alarm systems that 
support 5800 series devices. Refer to control/communicator 
installation instructions for compatibility. 
The detector consists of an electrochemical carbon monoxide sensor 
assembly coupled to a wireless transmitter. The transmitter can 
send alarm, trouble, tamper, and battery condition messages to the 
system’s receiver. Refer to the wireless system’s instructions for the 
maximum number of transmitters that can be supported. 
NOTICE: This manual should be left with the owner/user of this 
equipment. 
IMPORTANT: This detector must be tested and maintained 
regularly following NFPA 72 requirements. 
WARNING: This product is intended for use in ordinary indoor 
locations of dwelling units, including homes, residential buildings, 
hotels, schools, dormitories, and day care centers. It is not intended 
for use in industrial factories or commercial parking garages. 
 
Detector Description 
• Listed to UL standard 2075 (pending) 
• Supervised 
• Local sounder 
• Dual LED’s 
• Test/Hush button 
• Surface mount to wall or ceiling 
• Optional drywall anchors included 
The 5800CO contains a piezoelectric horn which generates the 
ANSI S3.41 temporal 4 pattern in an alarm condition (see note 
below Table 1 for temporal 4 pattern). In alarm, a message is also 
sent to the wireless control panel and the detector’s zone number is 
displayed at the console. The alarm message is transmitted every 4 
seconds until the carbon monoxide condition has cleared and the 
detector has reset. During an alarm condition, pressing the 
detector’s test button will silence the piezoelectric horn for 5 
minutes. Once the detector has reset, a RESTORE message is 
transmitted to the control panel and the transmitter’s zone number 
can be cleared from the panel. The mounting base installation is 
simplified by the incorporation of features compatible with drywall 
fasteners or other methods that provide a method for securing the 
detector in place. 
During initial power-up, the red and green LEDs will blink together 
once every 10 seconds up to four times. It takess about 30 seconds 
for the detector’s CO sensor to stabilize (see Table 1). 
After power-up has completed and the detector is functioning 
normally within its listed sensitivity range, the green LED blinks 
once every 10 seconds. The LED indication must not be used in 
place of the tests specified under TESTING THE DETECTOR. In 
a trouble condition, the red LED will blink once every 10 seconds 
(refer to Table 1). If the detector senses a low battery condition, the 
red LED blinks once every 45 seconds. 
Two LEDs and a sounder on the detector provide local visual and 
audible indication of the detector’s status as listed in Table 1. 
Table 1: Detector LED Modes 
 
Green LED 
Red LED 
Sounder 
Normal (standby)  Blinks every 
10 seconds 
Off Off 
Alarm/Test Off 
Blinks every 
1 second 
Temporal 4 
Pattern
 
Low Battery 
Off 
Blinks every 
45 seconds 
Chirp every 45 
sec after LED 
blinks for 7 days 
Communication 
Fail 
Off 
Blinks every 
5 seconds 
Off 
Trouble Off  Blinks every 
5 seconds 
One chirp every 
45 seconds 
Detector End-of-
Life 
Off 
Blinks every 
10 seconds 
Off 
Power Up 
Blinks every 
10 secs
††
 
(w/red LED)
 
Blinks every 
10 secs 
††
 
(w/green LED)
 
Off 
† Temp 4 pattern is repeated pattern of four short beeps followed by 
a five second pause. When the detector has been in alarm for 30 
minutes, the alarm signal will be given once every minute. If 
ambient conditions return to normal, the detector will self-restore 
out of alarm and into Normal (standby) mode. 
†† Red and green LEDs blink a total of four times, once every 10 
seconds. 
Hush feature: If required, the audible alarm can be silenced for 5 
minutes by pushing the button marked “Test/Hush”. The red alarm 
light will continue to flash in temp-4 pattern. If carbon monoxide is 
still present after the 5 minute hush period, the audible alarm will 
sound. The hush feature will not operate at levels above 350 ppm 
(parts per million) carbon monoxide. 
Trouble feature: When the sensor supervision is in a trouble 
condition, the detector will send a trouble signal to the panel. 
Trouble conditions include an open circuit, sensor removal 
(tamper), and sensor end of life. 
End of Life Timer feature: When the detector has reached the 
end of its life, the trouble contact will open. This indicates that the 
CO sensor inside the detector has passed the end of its life and 
must be replaced. This detector’s lifespan is approximately six 
years from the date of manufacture. Refer to Detector Replacement 
section 
Low Battery Detection:
 
The 5800CO is powered by a single 3-
volt CR123A or DL123A Lithium battery (included). The detector 
checks for a low battery at least every 65 minutes. If a low battery 
is detected, the transmitter sends a low battery message to the 
control panel, which beeps and displays the detector’s zone number. 
In addition, the red LED of the detector will blink every 45 seconds 
and the test button will be disabled. This condition will exist for a 
minimum of 7 days, and then the detector’s horn will “chirp” about 
every 45 seconds. Pressing the test button during this time will 
silence the chirps for 12 hours. The battery should be replaced 
BEFORE the chirps begin. Be sure to replace the battery with a 
fresh one. 