WIRELESS THERMOSTAT
69-1535
6
Table 3. Thermostat Installer Setup Options.
Select
Installer Setup 
Number 
(Press Time s 
key to 
change)
Factory Setting
Other Choices
(Press
 ▲ 
or
 ▼
 key to change)
Actual
Setting
Display
Description
Display
Description
Not used
1
Fan operation
a
2
0
Conventional 
applications where 
equipment controls 
fan operation in heat 
mode
1
Heat pump or electric heat 
applications where 
thermostat controls fan 
operation in heat mode
Not used
3
Heating cycle 
rate 
4
6
6—6 cph used for 
conventional heat
1, 3 or 9
1—1 cph used for radiant 
floor heat, gravity system
3—3 cph used for hot 
water systems or high 
efficiency furnaces
9—9 cph used for electric 
heat systems
Not used
5 thru 11
System setting 
adjustment 
12
1
Manual changeover 0 or 2
0—Auto changeover
2—Auto only 
Adaptive 
Intelligent 
Recovery™ 
control
13 
0
Adaptive Intelligent 
Recovery™ control 
is activated (system 
starts early so 
setpoint is reached 
by start of program 
period)
1
Conventional recovery 
(system starts recovery at 
programmed time)
Degree 
temperature 
display
14
0
Temperature is 
displayed in °F
1
Temperature is displayed 
in °C
Not used
15
Clock format 
16
0
12-hour clock format 1
24-hour clock format
Not used
17 and 18
Extended fan 
operation in 
heating
a
19 
0
No extended fan 
operation after the 
call for heat ends
1
Fan operation is extended 
90 seconds after the call 
for 
heat ends.
Extended fan 
operation in 
cooling
a
20 
0
No extended fan 
operation after the 
call for cool ends
1
Fan operation is extended 
90 seconds after the call 
for 
cool ends.
Not used
21 thru 29
Deadband 30 
3
Heating 
and 
cooling 
setpoints can be set 
no closer than 3°F 
(1.5°C)
4 thru 10
Heating and cooling 
setpoints can be set no 
closer than the chosen 
value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Not used
31 and 32
Minimum off 
time for the 
compressor
33
5
five-minute 
minimum off time for 
the compressor
0 thru 4
Minimum number of 
minutes (0 thru 5) the 
compressor will be off 
between calls for the 
compressor