Programming 
This section describes the basic steps for adding the sensor 
to panel memory. For complete instructions, refer to the 
specific panel’s documentation. 
To program the sensor: 
1.  Set the panel in program mode. 
2.  When prompted by the panel, enter the appropriate 
group number (groups 00 through 07). 
Note:  For UL installations where the holder is used, the 
sensor must be added as a fixed type (sensor groups 
00, 02, 04, or 05). 
3.  When prompted by the panel, select the desired sensor 
number. 
4.  When prompted by the panel, trip the sensor by 
pressing the sensor button. 
5.  Exit from program mode. 
Sensor Test 
To test the sensor: 
1.  Set the system to the Dealer Sensor Test mode. 
2.  Press the button on the sensor. 
3.  Count the number of signals received by the panel, 
indicated by interior siren beeps. Seven to eight beeps 
are considered acceptable. 
4.  Test the sensor from several locations within the 
premises to check for consistent response. 
Battery Replacement 
To replace the sensor battery: 
1.  To disassemble the sensor, remove the two screws on 
the back of the sensor and separate the front and back 
plastic. 
Caution:  You must be free of static electricity before 
handling the transmitter circuit board. Touch a 
grounded, bare metal surface before touching the 
circuit board, or wear a grounding strap. 
2.  Remove the old battery from its holder and install the 
new battery, observing polarity. 
Caution:  Install only the same size and type of battery. Do 
not substitute another size or type of battery. 
3.  Reassemble the sensor. 
Note:  Be sure to assemble the sensor correctly to ensure 
water resistance. Be especially careful not to nick or 
damage the rubber gasket lining. 
4. 
Test the sensor as described in “Sensor Test” above. 
Lithium Battery Disposal 
Lithium batteries that are no longer usable are considered 
hazardous waste. Be sure to properly dispose of the old 
battery. Contact your local city government for hazardous 
waste disposal laws. 
Specifications 
Compatibility 
All Interlogix Security Learn Mode panels 
Power source 
3.6 VDC Saft or Tekcell lithium battery 
Enclosure 
Water-resistant and shock-resistant 
Dimensions (LxWxD) 
2.25" x 1.75" x 0.75" (57.1 mm x 44.4 mm x 
19 mm) 
Regulatory Information 
Manufacturer 
UTC Fire & Security Americas Corporation, Inc. 
2995 Red Hill Ave, Costa Mesa, CA 92626 USA 
FCC / IC 
compliance 
This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation.  
Changes or modifications not expressly approved 
by Interlogix can void the user’s authority to 
operate the equipment. 
FCC ID: B4Z-697B1-PANIC 
IC ID: 1175C-697B1PANIC 
 
This device complies with Industry Canada 
license-exempt RSS standard(s). Operation is 
subject to the following two conditions: (1) this 
device may not cause interference, and (2) this 
device must accept any interference, including 
interference that may cause undesired operation 
of the device. 
Cet appareil est conforme aux normes RSS 
exemptes de licence d'Industrie Canada.  
Le fonctionnement est soumis aux deux 
conditions suivantes : (1) cet appareil peut ne pas 
provoquer d’interférences et (2) cet appareil doit 
accepter toutes interférences, y compris les 
interférences pouvant provoquer un 
fonctionnement non désiré de l’appareil.  
U.S. patents 
4,855,713, 4,864,636, and others pending. 