UTC Fire & Security Americas Corporation Inc 773A-SMOKE User Manual

Page of 6
2
ESL Smoke Sensor Model 562
Mounting Guidelines
Preliminary
ity roo, and hallways not protected by the required 
smoke alarms. The installation of smoke alarms in 
kitchens, attics (finished or unfinished), or garages is 
not normally recommended, as these locations occa-
sionally experence conditions that can result in 
improper operation.”
The above NFPA standards are a minimum 
requirement for smoke sensor installation. For better 
protection, we also require the installation of a smoke 
sensor inside every bedroom in existing construction.
DO NOT mount a smoke alarm to a drop ceiling tile; 
mount it to a metal runner (see figure 2).
Figure 2. Smoke alarm mounted to drop ceiling.
Mount all smoke alarms within 100 feet of the panel.
Install a minimum of two smoke alarms in any house-
hold, no matter how small it is.
Put a smoke alarm in the hallway outside of every bed-
room area. A minimum of two smoke alarms are 
required in homes with two bedroom areas (see 
figure 3).
A78-1171-02
Figure 3. Residence with multiple sleeping areas
Put a smoke alarm on every level of a multi-level resi-
dence (see figure 4).
Figure 4. Multi-level residence
Install basement alarms on the ceiling at the bottom of 
the basement stairwell.
Install smoke alarms on the ceiling as close to the cen-
ter of the room as possible. If this is not practical, 
install it on the ceiling no closer than 4 inches (10 cm) 
from any wall or corner (see figure 5).
If ceiling mounting is not practical, install on an inside 
wall between 4 and 6 inches (10 and 15 cm) from the 
ceiling (see figure 5).
Put smoke alarms at both ends of a bedroom hallway if 
the hallway is more than 30 feet (9 meters) long. Large 
rooms over 900 square feet require more than a single 
sensor.
Figure 5. Smoke alarm mounting locations
Areas with rough ceilings or short, transom-type walls 
coming down from the ceiling require additional smoke 
alarms.
Install second-floor smoke alarms on the ceiling at the 
top of the first-to-second floor stairwell. Be sure no 
door or other obstruction blocks the path of smoke to 
the unit.
In rooms with sloped, peaked, or gabled ceilings, 
install smoke alarms 3 feet (0.9 meter) measured down 
on the slant from the highest point of the ceiling (see 
figure 6).
Figure 6. Sloped, peaked, or gabled ceilings
Limitations
All alarms are subject to possible compromise or failure-to-
warn for a variety of reasons, for example:
Smoke alarms cannot detect smoke in chimneys, walls, 
roofs, or smoke blocked by a closed door.
Alarms may not detect smoke on other levels of the 
building.
BEDROOM
SMOKE DETECTORS FOR
MINIMUM PROTECTION
SMOKE DETECTORS FOR
MORE PROTECTION AND 
REQUIRED IN NEW CONSTRUCTION
BEDROOM
BEDROOM
LIVING ROOM
DINING
ROOM
KITCHEN
FAMILY ROOM
BEDROOM
BEDROOM
BEDROOM
LIVING
ROOM
KITCHEN
BASEMENT
GARAGE
SMOKE DETECTORS FOR MINIMUM PROTECTION
SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
BEST LOCATION
ACCEPTABLE LOCATION
DEAD AIR
SPACE
BEST IN CENTER
OF CEILING
NO CLOSER THAN 4
" (10 cm)
FROM SIDE WALL
MOUNT ON WALL
AT LEAST 4
" (10 cm)
FROM CEILING
NO MORE
THAN 6
" (15 cm)
FROM CEILING
HORIZONTAL
DISTANCE
FROM PEAK
3 FEET
(.9M)