4. Setting Up for Initial Operation
MR Booster Manual: (MN001808-1, 9/99)
Page 35
Basic steps to set up alarms in the repeater:
1. Set thresholds
2. Set alarm criticality
3. Set external I/O (optional)
Example
The following example shows how to set output relay one to open when PA
temperatures exceed +80C.
First, set the alarm threshold:
1. At the > prompt, type SET; press Enter.
2. From the menu prompt, type D; press Enter.
3. Type C; press Enter. (For Max PA Temp - Alarm Point)
4. Type 80; press Enter.
Second, set the alarm criticality:
5. Type E; press Enter. (For the Critical Alarms Menu)
Alarms
A  Max Power Supply Temp - Alarm Point...+85 Deg C
B  AC Power Fail - Alarm Point...........10.0 Minutes
C  Max PA Temp - Alarm Point.............+90 Deg C
D  External I/O..........................NORMAL STATES
E  Critical Alarms.......................NO ALARMS REPORTED
Critical Alarms
A  PA POWER HI ALARM.....................LOG ONLY
B  PA POWER LO ALARM.....................LOG ONLY
C  PA TEMP HI ALARM......................LOG ONLY
D  PA OUT-OF-SERVICE ALARM...............LOG ONLY
E  PA OVERCURRENT/OVERDRIVE ALARM........LOG ONLY
F  POWER SUPPLY TEMP HI ALARM............LOG ONLY
G  AC POWER LOST ALARM...................LOG ONLY
H  POWER SUPPLY REGULATION ALARM.........LOG ONLY
I  VSWR HI ALARM.........................LOG ONLY