Eaton V70BF3-N-SL-115 User Manual

Page of 5
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 
4
Option 4: EMI/RFI Filtering
Choose “N” for no filtering or “F” for filtering. See below for filtering specifications.
Option 5: Receptacle Type
Choose either straight blade or twist lock style receptacles. See the table in Option 1 for a view of the available receptacles. 
The receptacles are referred to by their NEMA designation number.
Option 6: Plug Type
Choose either straight blade or twist lock style plug. See the table in Option 1 for a view of the available plug styles. The plug is referred 
to by the NEMA designation number. Verify you have the correct type of mating receptacle available at your facility. Plug types limit the available 
voltage and current options.
Option 7: Current Meter
This unit is available with or without a front panel digital current reference meter. This two-segment current reference meter will 
display the current value of the connected load. (The meter is an AC averaging meter.) This allows you to properly load your 
Power Distribution Unit to avoid an overload situation. This can also be used for monitoring to detect a fault before it occurs. 
The display shows two digits with no decimal place. The meter is accurate to +/- 1 amp with 1 amp resolution. 
The current meter 
option is not available on the following versions: G1 and J1
Option 8: Power Cable Length
The power distribution unit has either SO, SOOW or SJT type power cable. The length can be specified as 9 feet or 15 feet. 
The maximum length allowed by UL standards for an attached power cable is 15 feet. For permanent installations exceeding 15 feet, 
a licensed electrician should install a permanent circuit. Extension cords should only be used for temporary installations. The AB version comes 
with an IEC C20 power inlet. The power cable must be ordered separately for this version. 
See options below.
EMI/RFI FILTERING COMMON MODE INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
6
19
28
42
45
50
DIFFERENTIAL INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
2
40
60
65
57
55
Environmental
Operating Temperature is 0 to 50 C
Storage Temperature is -40 to 70 C
Altitude Maximum 10,000 ft.
Relative Humidity is 95% Max Non-Condensing
010-9334:
C19 to NEMA 5-15P
125V, 15A Straight Blade
8 foot, 14AWG/3wire
010-9335:
C19 to NEMA 5-20P
125V, 20A Straight Blade 
8 foot, 12AWG/3wire
010-9339:
C19 to NEMA L5-20P
125V, 20A Twist-Lock 
8 foot, 12AWG/3wire
010-9341:
C19 to NEMA L6-20P
250V, 20A Twist-Lock 
8 foot, 12AWG/3wire
010-0025: 8 foot
C13 to C14 Harmonized, 1mm/3wire
100-240V rated
010-9343:
CEE7-7 to C19 
250V, 16A EUROPE (Schuko) 
2.5M, 1.5mm/3wire Harmonized
EMI/RFI FILTERING COMMON MODE INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
6
19
28
42
45
50
DIFFERENTIAL INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
6
6
30
50
30
30