IDEAL Model SCL1000 Smart Connector Installation Instructions
WARNING: This is a current rated device. Use in applications involving
amperage beyond its rating can be dangerous and cause electrical fires.
Wiring must comply with all applicable electrical codes.
Turn off power before removing or installing connector.
Turn off power before removing or installing connector.
TERMINOLOGY
LINE: Incoming power feed from premise wiring
LOAD: Power output from Smart Connector to ballast AC power input
DIM: 0-10 VDC dimming control output from Smart Connector to ballast dimming
input
CONNECTING THE WIRES
LINE: Incoming power feed from premise wiring
LOAD: Power output from Smart Connector to ballast AC power input
DIM: 0-10 VDC dimming control output from Smart Connector to ballast dimming
input
CONNECTING THE WIRES
LINE Connector
The LINE Connector accepts 12 AWG-18 AWG copper conductors, solid or stranded (19
strands or less for 12 AWG-16 AWG, 7 strands or less for 18 AWG).
Use only one conductor per port and ensure that no copper is exposed on any of the
wires after installation.
1.
The LINE Connector accepts 12 AWG-18 AWG copper conductors, solid or stranded (19
strands or less for 12 AWG-16 AWG, 7 strands or less for 18 AWG).
Use only one conductor per port and ensure that no copper is exposed on any of the
wires after installation.
1.
Strip wires to 1/2”.
2.
Grip LINE hot wire and firmly push conductor into one of the black LINE ports. See Fig. 2.
3.
Grip LINE neutral wire and firmly push conductor into one of the unmarked LINE ports. See
Fig. 2.
LINE Connector
LOAD
Connector
DIM Connector
Fig. 1
Fig. 2
LINE hot & feed-through
LINE neutral & feed-through
LOAD hot (black)
& neutral (white)
Antenna
LINE
Connector
LOAD
Connector