Relative humidity measurement 
Humidity display format: 
Percentage RH 
(Humidity data is only for thermostat internal use. It is displayed in test mode 
only. Humidity information is not available to end users.) 
Display / measurement range 
20% ~ 95% in 1% resolution 
Humidity measurement accuracy: 
+/-8% at 60%, 25°C 
+/-10% full measurement range. 
 
Temperature Control 
Temperature setting range: 
(Program, Temporary hold and 
Permanent Hold) 
Heating and cooling: 
Fahrenheit: 41°F ~ 95°F, 1°F setting resolution 
Celsius: 5°C ~ 35°C, 1°C setting resolution 
Heating setpoint cannot be set higher than cooling in the same program. 
Temperature setting range: 
(Vacation hold) 
Heating only 
Fahrenheit: 32°F ~ 60°F, 1°F setting resolution 
Celsius: 0°C ~ 15°C, 1°C setting resolution 
Switching differential (span): 
Stage 1:  
Fahrenheit: 0.5°F, 1.0°F and 2.0°F user selectable. 
Celsius: 0.2°C, 0.5°C and 1.0°C user selectable. 
Stage 2: 
Fahrenheit: 2.0°F (fixed). 
Celsius: 1.0°C (fixed). 
Stage 3: 
Fahrenheit: 2.0°F (fixed). 
Celsius: 1.0°C (fixed). 
Auto season changeover deadband: 
Fahrenheit: 5°F ~ 11°F, 1°F setting resolution 
Celsius: 2.5°C ~ 6°C, 0.5°C setting resolution 
Temperature control accuracy: 
Base on NEMA test result: 
Span set to minimum. Total loading 2.5A. After control is stabilized, the 
following should be achieved: 
Differential: less than 2°F 
Droop: less than +/-1°F 
 
Control protection 
Compressor short cycle protection timer: 
5 ~ 10 minutes, 1 minute setting resolution. 
Set through network. 
Residual Cooling fan delay timer: 
30 ~ 300 seconds, 30 seconds setting resolution. 
Set through network. 
Auto heat cut-off: 
When room temperature is higher than 99°F or 35°C. 
Auto cool cut-off: 
When room temperature is lower than 40°F or 5°C. 
Temperature error cut-off: 
When error is found in room temperature measurement. 
 
Filter counter 
Filter counter: 
Counts Y1 or G turn on time for up to 999 hours.  
Filter change reminder: 
300, 500 or 700 hours user selectable. 
Indication on LCD when Filter counter reached the reminder setting.