Cinch Systems Inc RF-CHW-FIRE User Manual
The IQ Hardwire 16-F offers a cost effective way of integrating hardwired security & smoke
detector zones with the IQ Panel 2. It includes backup battery charging, 500mA of 12volt
auxiliary power, an onboard siren relay, built-in status LED’s for each zone and support for
up to 10 two-wire smoke detectors. Normally Open and Normally Closed contacts are
supported as well as powered zones like motion sensors and glass break detectors.
detector zones with the IQ Panel 2. It includes backup battery charging, 500mA of 12volt
auxiliary power, an onboard siren relay, built-in status LED’s for each zone and support for
up to 10 two-wire smoke detectors. Normally Open and Normally Closed contacts are
supported as well as powered zones like motion sensors and glass break detectors.
Note: Not for use with CO detectors
QUICK GUIDE
INFORMATION
TECHNICAL SPECIFICATIONS
Document #: IQHW16FQG
Revision Date: 4/18/18
Revision Date: 4/18/18
Qolsys Part #: QS7133-840
STEP 1: INSTALL THE HARDWARE
UL REQUIREMENTS
If mounting inside a
metal can, the antenna
must extend outside the
enclosure to ensure RF
communication
Confidential &
Proprietary.
Made in Taiwan.
Full installation
manual and other
documentation
available at
Qolsys.com.
Proprietary.
Made in Taiwan.
Full installation
manual and other
documentation
available at
Qolsys.com.
Page of 3 Qolsys Confidential and Proprietary.
1
Input Voltage: 16.0VDC Plug-In Transformer
Backup Battery: 12VDC 5AH Max (not included)
Dimensions: 5.5” X 3.5”
Operating Temperature: 32 to 122F (0 to 50C)
Humidity: 95% RH Max
EOL Supervision: 4.7k Ohm
Input Zones: 15 N/O or N/C
Smoke Zone: 1 two-wire smoke loop, 10
detectors max. Support for System Sensor® 2W-
B, 2WT-B, 2WTA-B.
Auxiliary Voltage Output: 12VDC @ 500mA
Tamper Zone: Used for case tamper, no resistor
Relay Contact: 60VDC/1A Max drives siren
Backup Battery: 12VDC 5AH Max (not included)
Dimensions: 5.5” X 3.5”
Operating Temperature: 32 to 122F (0 to 50C)
Humidity: 95% RH Max
EOL Supervision: 4.7k Ohm
Input Zones: 15 N/O or N/C
Smoke Zone: 1 two-wire smoke loop, 10
detectors max. Support for System Sensor® 2W-
B, 2WT-B, 2WTA-B.
Auxiliary Voltage Output: 12VDC @ 500mA
Tamper Zone: Used for case tamper, no resistor
Relay Contact: 60VDC/1A Max drives siren
1. Mount the IQ Hardwire 16-F vertically in your desired location
2. Install the provided antenna into the “ANT” terminal at the top of the unit free from
2. Install the provided antenna into the “ANT” terminal at the top of the unit free from
obstructions
3. Wire all hardwired sensors into the terminals marked Zone 1-15. Zone 16 is reserved
for two-wire smoke detectors:
a. All zones must have a 4.7k resistor (included) installed in either the N/O
(parallel) or N/C (series) position
b. Wire the positive and negative leads from powered devices, such as motion
sensors and glass break detectors, into the “AUX” (+) and “GND” (-) terminals to
power the devices.
power the devices.
c. Wire a tamper switch into the tamper terminals without using a resistor. If a
tamper switch is not being used, permanently shunt the zone with a piece of
wire.
wire.
d. Optional: Wire the hardwired siren (60VDC/1A Max, see wiring diagram)
4. Plug in a 5Ah lead acid backup battery with included battery leads (battery not
included)
5. Using the provided 16vDC power supply, connect the leads to the terminals marked
“+16.0V” & “GND”, then plug then supply into a wall outlet. (Note: dashed wire is
positive)
positive)