Ever Poweline 31 - 15kVa/10,5kW T/PWRLTO-315K00/00 User Manual
Product codes
T/PWRLTO-315K00/00
PROTECTION
Overload protection
Overload is signalled by a series of LED lights on the LCD and a continuous sound. If the load is 105-130% of the
maximum load, the UPS switches to the BYPASS mode after 10 minutes. If the load is greater than 130%, the UPS
switches to BYPASS mode after one second and cuts off output power after 1 minute.
maximum load, the UPS switches to the BYPASS mode after 10 minutes. If the load is greater than 130%, the UPS
switches to BYPASS mode after one second and cuts off output power after 1 minute.
Short circuit protection
Short circuit is indicated by a series of LED lights on the panel and a sound. After a short circum power on the output
is cut off. If the UPS is switched off during a short circuit indication, but the short circuit is not removed, the UPS
switches to BYPASS mode, which activates the input automatic fuses.
is cut off. If the UPS is switched off during a short circuit indication, but the short circuit is not removed, the UPS
switches to BYPASS mode, which activates the input automatic fuses.
POWERLINE 3-1
10-31, 15-31, 20-31
INSTALLATION GUIDELINES
POWERLINE 3-1
www.ever.eu
PARAMETER / UPS
POWERLINE 10-31
POWERLINE 15-31
POWERLINE 20-31
Power
10kVa/7kW
15kVA/10.5kW
20kVA/14kW
POWER SUPPLY PARAMETERS
Power supply topology
3P5W
3P5W
3P5W
Voltage range
304 - 478V AC
304 - 478V AC
304 - 478V AC
Frequency
50/60HZ +/- 4Hz
50/60HZ +/- 4Hz
50/60HZ +/- 4Hz
Frequency range
+/-4H
Z
+/-4H
Z
+/-4H
Z
PF
>0,98
>0,98
>0,98
Maximum current
50A AC
75A AC
100A AC
Minimum wire section surface area
10mm
2
16mm
2
25mm
2
Line protection
3 x D50A
3 x D100A
3 x D100
BATTERY PARAMETERS
Nominal voltage
240V DC
240V DC
240V DC
Maximum current
40A DC
60A DC
80A DC
Minimum wire section surface area
not applicable
16mm
2
25mm
2
Line protection
internal
internal
internal
OUTPUT PARAMETERS
Nominal voltage
220/230/240V AC
220/230/240V AC
220/230/240V AC
Frequency
synchronous/50Hz
synchronous/50Hz
synchronous/50Hz
Frequency tolerance
0.1Hz
0.1Hz
0.1Hz
Maximum current
45A AC
68A AC
91A AC
Minimum wire section surface area
10mm
2
16mm
2
25mm
2
Line protection
2 x B50A (chk B)
2 x B100A (chk B)
2 x B100A (chk B)
ENVIRONMENT
Working temperature
0 - 40°C
0 - 40°C
0 - 40°C
Storage temperature
0 - 40°C
0 - 40°C
0 - 40°C
Humidity
<95%
<95%
<95%
Altitude above sea level
<1,000m
<1,000m
<1,000m
MECHANICAL PARAMETERS
Dimensions - (height x width x depth)
260 x 570 x 717mm
260 x 570 x 717mm
260 x 570 x 717mm
Battery pack weight
39 kg
55 kg
55 kg
Operating distance
Front: >200mm
Sides: >100mm
Back: >300mm
Front: >200mm
Sides: >100mm
Back: >300mm
Front: >200mm
Sides: >100mm
Back: >300mm