56   OI/266/WIHART-EN | 2600T Series Pressure transmitters
9 Troubleshooting
9 Troubleshooting
9.1 Overview
This section provides troubleshooting suggestions for the most 
common problems occuring in the field.
Important. Procedures described in the following paragraphs 
will help the user to verify that 266 pressure transmitter and 
wireless communication network are correctly in place.
9.2 Device-related issues
9.2.1 Device does not power on
When the user receives a 266 WirelessHART pressure 
transmitter, the first step to be taken is to power the device on. 
After removing the battery pull-tab grabbing it firmly and pulling  
the cell will give power supply to the electronic module LCD 
display will go live for 30 seconds and then it will go off. 
If this doesn’t happen the possible cause could be:
Possible cause
Solution
Battery discharged
Change the battery (spare part number 
DR3051)
Display or battery not well 
connected
Check HMI contacts or invert battery position 
into the terminal block
Terminal block defect
Check battery and terminal blocks contacts
In case the device is not powering, please check if the battery 
is still in good conditions and it has not been exposed to high 
temperatures for long periods of time. To install a new battery, 
please follow below instructions
  1.  Install 266 WirelessHART pressure transmitter properly,    
    according to ABB practices explained in the present  
 
    document using an approved thread sealant on all  
 
   connections.
  2.  Unscrew the battery cover from the wireless device.  
 
    Battery lays on the opposite side of the display (if installed)  
    as indicated by the writing “Field Terminals” engraved on   
    housing neck. 
  3.  Remove and replace the battery paying attention to the    
   polarity. 
Note. Wireless devices should be powered up only during the 
network setup and beginning with the closest device to the 
Gateway. This will result in a simpler and faster network installation. 
For further information about the battery, please refer to paragraph 
6.6 of this document.
  4.  Close the housing cover so as to have a metal-to-metal    
    contact but do not over tighten. If the installation of the    
    battery as been properly performed, the LCD display will   
    go live for 30 seconds and then it will go off.
Important. Battery part number is DR3051. To get spares batteries, 
please get in touch with your local ABB service reference. 
Replacements with non-ABB batteries is forbidden and will lead to 
certification invalidity. 
9.3 Network-related issues 
9.3.1 General
Network joining could represent a critical point for a wireless 
transmitter.
Basic preliminary setting for joining consists in writing two 
parameters both into the device and into the Gateway. These 
parameters are:
  — Network ID
  — Join Key
Important. Network ID and Join Key are to be always the 
same both on field instrument and Gateway.
It is also necessary to write the LONG TAG for communication 
via Ethernet TCP/IP within the Asset Vision Basic projects.
The above-mentioned parameters can be set using: 
  — Asset Vision Basic wired to device dedicated terminals    
    through a HART modem.
  — Hand-held terminal wired to device dedicated terminals
  — Local HMI menu 
9.3.2 Device does not join the network
After the basic settings have been correctly executed, a typical 
anomalous situation is that the device does not join to the 
wireless network.
Network is joined when the radio signal icon 
 is steady 
visible on the upper right-hand corner of the HMI (if installed). 
Possible cause
Solution
Power supply is missing
Access the “Z” button and depress it for few 
seconds until the display goes live. If this will 
not happen, see section 9.2.1
Anyway, device will more likely not join the network due to a 
radio signal failure. Radio failure can be identified thanks to the 
above-mentioned icon.