Unique Broadband Systems Ltd. DRU2KW User Manual

Page of 64
Page 15
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
10.0  LED Indicators
I
0
1
 
2
 
3
LOAD BREAKERS
I
0
I
0
I
0
I
0
CTR
MAJA
MINA
ACFA
RFA
OTA
OVA
CTR
MAJA
MINA
ACFA
RFA
OTA
OVA
1
2
3
4
5
GMT FUSES
1.............................10
1
 
2
 
3
Figure 5 - LED Indicators
During normal operation there will be one green LEDs displayed as shown in figure 5 above.
The LED indicators provide visual indication of both status and alarm conditions as described 
below:
 
CTR – 
GREEN
 – Indicates that the unit has power and is functioning normally.
 
MAJA – 
RED
 – Indicates a ‘Major’ (Immediate Response) alarm condition.
 
MINA – 
RED
 – Indicates a ‘Minor’ (Scheduled response) alarm condition.
 
ACFA – 
RED
 – Indicates an AC supply failure.
 
RFA – 
RED
 – Indicates a Rectifier module failure.
 
OTA – 
RED
 – Indicates that one or more of the monitored temperatures is too high.
 
OVA – 
RED
 – Indicated that the system Bus Voltage is too high.