Unique Broadband Systems Ltd. DRU2KW User Manual

Page of 64
Page 55
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Parameter Name
Function
rectifierOCA
Rectifier over current alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
loadOCA
Load over current alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
batteryOCA
Battery over current alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
batteryODA
Battery on discharge alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
digitalAlarm
x
(x = 1 to 16)
Digital input 
x
 alarm. [1 only in X75]
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
nRectAlarm
Insufficient rectifiers alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
acfAlarm
AC Failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
rectThermalAlarm
Rectifier thermal alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
rectFanAlarm
Rectifier fan alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
singleRFA
Single rectifier failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
multiRFA
Multiple rectifier failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
eqAlarm
Equalization active alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bTestAlarm
Battery test active alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bProbe
x
DisAlarm
(x = 1 or 2)
Battery temperature probe 
x
 disconnected alarm. [1 only in X75]
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bProbe
x
ShortAlarm
(x = 1 or 2)
Battery temperature probe x shorted alarm. [1 only in X75]
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
extProbeDisAlarm
External temperature probe disconnected alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
extProbeShortAlarm
External temperature probe shorted alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bTestFailAlarm
Battery test failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
digitalInput
x
(x = 1 to 16)
Digital input is Closed (0) or Open (1). [1 only in X75]