X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
3.0   SAFETY  WARNINGS
3.1 
The X75 Compact DC Power System operates at voltages that could potentially be 
hazardous.  Furthermore, inadvertent short circuiting of the system battery and/or 
rectifier by mis-connection or other error could be harmful.  This product should be 
handled, tested and installed only by qualified technical persons who are trained in 
the use of power systems and are well aware of the hazards involved.
3.2
 
All connections to the X75 should be carefully checked for errors before applying 
power to it.
3.3
Specific Considerations for Rack Mounted Equipment
 
3.3.1 Elevated Operating Ambient - If installed in a closed or multi-unit rack 
assembly, the operating ambient temperature of the rack environment may be greater 
than room ambient.  Therefore, consideration should be given to installing the X75 
in an environment compatible with the maximum ambient temperature of 50°C at 
full rated load, and at 70°C at derated load at a derating factor of 2.5%/°C from 
50°C to 70°C.
3.3.2 Reduced Air Flow - Installation of the X75 in a rack should be such that the 
amount of air flow required for safe operation of the equipment is not compromised.
3.3.3 Mechanical Loading - Mounting of the X75 in the rack should be such that a 
hazardous condition is not achieved due to uneven mechanical loading.
3.3.4 Circuit Overloading - Consideration should be given to the connection of the
X75 to the supply circuit and the effect that overloading of the circuits might have 
on over-current protection and supply wiring.  Appropriate consideration of the X75 
nameplate ratings should be used when addressing this concern.
3.3.5 Reliable Earthing - Reliable earthing of rack-mounted equipment should be 
maintained.  Particular attention should be given to supply connections other than 
direct connections to the branch circuit (e.g. use of power strips).”
3.4
 
The X75 is intended only for installation in a “RESTRICTED ACCESS LOCATION”.
3.5 
Input/output short circuit ratings are 5KA AC for terminals connected to breakers 
and 450A AC for terminals connected to GMT type fuses.