6 Using the product 
20 
6.4. 
Measuring  
6.4.1. 
Volume flow measurement 
✓  The volume flow hood is fitted. 
1.  Switch on the instrument.  
2.  In the instrument settings, set the application volume flow hood 
and also the required measurement program: 
Single measurement or Continuous measurement.  
3.  Press 
►, ■
 on the testo 420, or the trigger on the measurement 
base to hold or start and stop the measurement.  
4.  Press   to save the measurement data. Unsaved 
measurement data is lost once you carry out the next 
measurement.  
-  The target folder and file name are displayed, confirm with 
 
to save the measurement data under this name and in the 
selected folder. 
6.4.2. 
Pitot tube measurement 
1.  Remove the testo 420 from the measurement base. 
2.  Connect the hoses to the testo 420 and to the Pitot tube.  
3.  Press   -> 
Application
 -> 
Pitot tube
 and there set the duct 
geometry, the Pitot tube factor and the temperature, and 
choose between actual and standard. 
4.  Select the required measurement program. 
5.  Carry out the measurement.  
6.  Press   to save the measurement data. Unsaved 
measurement data is lost once you carry out the next 
measurement.  
-  The target folder and file name are displayed, confirm with 
 
to save the measurement data under this name and in the 
selected folder. 
6.4.3. 
Differential pressure measurement 
1.  Remove the testo 420 from the measurement base. 
2.  Connect the hoses to the testo 420 at + and -.  
3.  Press   -> 
Application
 -> 
Pressure only