Module
200 kW Frame
400 kW Frame
Weight
2,650 lbs
20,700 lbs*
38,000lbs*
Length
9.3'
19' 10.5"
40’
Height
8.6’
9.5’
9.5’
Width
3.3’
8.0’
8.0’
IT airflow
5,000 cfm
20,000 cfm
40,000 cfm
Outside airflow
7,000 cfm
28,000 cfm
56,000 cfm
Nominal Cooling Capacity
50 kW
200 kW
400 kW
Technical Specifications
©2011 Schneider Electric. All Rights Reserved. Schneider Electric and EcoBreeze are trademarks owned by Schneider Electric Industries SAS or its affiliated companies.  
All other trademarks are property of their respective owners. • 998-4515
Economization Comparisons
*Approximate operating weight with ducting
1. Hot aisle containment 101.48º F Return to A/C
2. Supply air/cold aisle 77° F
3. Bin Weather Data Saint Louis, Mo.
4. Does not reflect humidification losses
5. All systems should have fan control proportional to IT load of design
System Architecture
Partial PUE
kW - Hr/Yr
Relative power
1 MW Design Data @ 60% Load
EcoBreeze
1.09
466,518
45 %
Air econ w/heat wheel
1.10
503,999
48 %
Water-cooled chiller w/econ
1.14
728,195
70 %
Air-cooled chiller w/econ
1.16
846,039
81 %
Fresh air econ
1.14
718,159
69 %
DX fluid-cooled CRAC w/econ
1.20
1,044,073
100 %