Valeport Ltd 0804IDU User Manual
HydrINS 2 / HydrINS 2 Mini flow meter
Installation Manual
Page 28 / 83
5.2 Method for installation at 1/8
Figure 16: Diagram of installation at 1/8 diameter
For an installation at 1/8 diameter, the distance Z
1/8
after probe insertion
must be equal to:
Z
1/8
= L - E - 1/8 DI
Z
1/8
: Distance between the lower edge of the guide bar and the
top of the pipe (mm or in)
E: Pipe thickness (mm or in)
D: Inside diameter of pipe (mm or in)
L: Length (mm or in) – value according to model, equal to the
distance between the lower edge of the guide bar and the two
measurement electrodes located on the sensor
distance between the lower edge of the guide bar and the two
measurement electrodes located on the sensor
Model
L mm (inches)
300
760 (29.92)
500
935 (36.81)
700
1175 (46.26)
1000
1475 (58.07)
Mini
575 (22.64)
Table 2: Correspondence of lengths L with the HydrINS probe model for an installation at
1/8th diameter
Z
1/8
E
1/8 DI
DI
Guide Bar