Eaton V7HC13E32-4-009 User Manual

Page of 4
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 

Option 1
C13 
= Outlet style is IEC 60320 C13
rated at 15 amps in North America
C19 = Outlet style is IEC 60320 C19 
rated at 20 amps in North America   
V 7 H
-
V7H “Design Your Own” part number guide
Option 
= 208 volt output   
Option 3
50 
= 50 amp input and plug
60 = 60 amp input and plug  

- 0
Option 6
09
 = 9 foot power cable
15 = 15 foot power cable  
 
Option 5
0
 = No current meter
  
 
Option 4

 = 2 pole plus ground input plug
(Line-Line-Ground) 1 phase
3 = 3 pole plus ground input plug
(Line-Line-Line-Ground) 3 phase delta
4 = 4 pole plus ground input plug
(Line-Line-Line-Neutral-Ground) 
3 phase wye  
 
PHYSICAL
•  Vertical mount 
• 
V70: Height 70” including mounting brackets 
  Height 66” without mounting bracket    
  attached. Width 2.0” x Depth 2.14”  
  (3.39” at circuit breaker cover)
•  18 gauge steel, powder coat black with   
    white silkscreen
•  Detachable mounting brackets allow for  
  several mounting options
BRANCH CIRCUIT PROTECTION
•  Six 2 pole 20 amp circuit breakers 
  are located on the front panel
•  UL 489 Listed electromagnetic 
  circuit breakers
•  Meets branch circuit breaker   
 
  requirements
•  Switch is flush with panel when “on” to 
  prevent accidental shut off
•  Switch shows red when in the off or tripped  
  position (no indicator lights)
POWER INPUT
•  Rear panel power cable is attached 
  via strain relief
•  Cable length options of 9 or 15 feet
POWER OUTLETS
•  C13 versions have (24) IEC 60320 type C13  
  receptacles
•  Each circuit breaker protects two receptacles
•  C19 versions have (12) IEC 60320 type C19  
  receptacles
•  Each circuit breaker protects one receptacle
HIGH CURRENT OUTPUT
•  Input options of 50 amps or 60 amps 
•  Single or three phase inputs are optional
•  Ideal for blade servers or other power 
  demanding applications
Red color indicates when the 
breaker is off. Circuit breaker 
switch is flush in the “ON” position 
to prevent accidental turn off.