iStarUSA IS-600S2UPD8 User Manual

Page of 11
Continuous 
10% 
Nominal AC Voltage 
50/60 Hz 
No loss of function or performance 
0 - ½ AC cycle 
30% 
Mid-point of Nominal AC 
Voltage  
50/60 Hz 
No loss of function or performance 
 
3. DC Output Specification 
 
3.1  Output Power / Currents 
Table 4: Load Range 
Voltage 
Minimum Continuous Load 
Maximum Continuous Load
1,3
 
+3.3V 0.5A  25A 
+5V 0.5A 25A 
+12V 0.8A  48A 
-12V 0.1A 0.5A 
+5VSB 0.1A  3.5A 
 
Notes: 
1: The +3.3 &+5 Volt total outputs shall not exceed 150W. 
2: Noise bandwidth is from DC to 20 MHz
 
 
3.2  Voltage Regulation, Ripple and Noise 
Table 5:    Regulation, ripple and noise 
Output Voltage 
+3.3V 
+5V 
+12V 
-12V 
+5VSB 
Load Reg. 
±5% 
±5% 
±5% 
±5% 
±5% 
Line Reg. 
±1% 
±1% 
±1% 
±1% 
±1% 
Ripple & Noise   
60mV 
60mV 
120mV 
120mV 
60mV 
Ripple and noise shall be measured using the following methods: 
a) Measurements made differentially to eliminate common-mode noise 
b) Ground lead length of oscilloscope probe shall be 
≤ 0.25 inch. 
c) Measurements made where the cable connectors attach to the load. 
d) Outputs bypassed at the point of measurement with a parallel combination of 
10uF tantalum capacitor in parallel with 0.1uF ceramic capacitors. 
e) Oscilloscope bandwidth of 0 Hz to 20MHz. 
f) Measurements measured at locations where remote sense wires are connected. 
g) Regulation tolerance shall include temperature change, warm up drift and dynamic load 
 
3.3 Capacitive 
Loading 
The power supply shall be stable and meet all requirements in the following table, except dynamic loading 
requirements.
 
Table 6: Capacitive Loading Conditions