Eaton 9135 UPS PPDM EPPDMG6000-3U-HWEU User Manual

Product codes
EPPDMG6000-3U-HWEU
Page of 57
INSTALLATION
EATON Two-in-One PPDM (5000/6000 VA) User's Guide  
S
  164201820 Rev 1  www.eaton.com/powerquality
26
Plug-Receptacle PPDM Installation
NOTE  Do not make unauthorized changes to the UPS or PPDM; otherwise, damage may
occur to your equipment and void your warranty.
To install the PPDM:
1.
Verify that the PPDM output circuit breaker is in the OFF position
(see Figure 9 on page 23).
2.
Verify that the bypass switch on the PPDM is in the NORMAL
position (see Figure 12).
Bypass Switch
Voltage Switch
Figure 12. PPDM (with Front Cover Removed)
3.
Changing the PPDM voltage switch setting. All high voltage outlets,
except the L14-30, use the UPS output voltage. The L14-30 and all
low voltage receptacles use the PPDM transformer, and the voltage
switch determines the voltage. See Table 3 for a complete list of
PPDM input/output voltage settings. Figure 12 shows the voltage
switch.
NOTE  In most applications, the voltage switch does NOT need changing.
To change the switch position, remove the bracket screw and turn
the switch. Flip the bracket around to fit the new position and
reinstall.