Eaton IPC3552-3685 Catalog

Page of 48
U
nde
rs
ta
ndi
ng ePDU technolog
ies
eaton corporation Enclosure Power Distribution Units
8
Why monitor?
The unique monitoring function of Eaton ePDUs allows you to remotely monitor the current draw of individual outlets or sections over 
a network. This, combined with state-of-the-art software, allows the user to aggregate the information from hundreds of ePDUs in one 
location. All monitored ePDUs also include the Easy-Read digital LED ammeter for easy start-up and provisioning of servers. This feature 
allows remote monitoring of current for capacity planning and energy management. 
Key features and benefits
•   Access circuit-level and ePDU-level information worldwide
•    Get a global view across your ePDUs from any PC or server with Intelligent Power
®
 Manager software  
(you can learn more about Intelligent Power Manager on page 9)
•   Receive warnings and alarms remotely
Advanced Monitoring
 
Advanced monitoring allows you to monitor down to the individual outlet.
Key features:
•  Monitor power consumption in kilowatt hours at the individual outlet level requirement 
•  Readings available via Ethernet connection over a network (utilizing Eaton’s Intelligent Power Manager software) 
•  Power consumption readings allow for power usage effectiveness (PUE) calculations 
•  Easy-read LCD screen reduces local monitoring time 
•  UL Listed (UL489) branch circuit breakers meet industry requirements 
•  Cisco EnergyWise Certified– Eaton’s new ePDUs are Cisco EnergyWise Certified 
400-volt solution
Eaton 400V ePDUs limit energy loss through transformers by avoiding the 480-208V conversion. These units use European standard, 
three-phase 400V phase-to-phase and 230V phase-to-neutral to replace 208V phase-to-phase in the U.S. Operating power supplies at 
230V versus 208V typically increases power supply efficiency.
400V ePDUs also distribute almost twice the power on the same copper to achieve multiple reductions. Eaton offers a unique power 
distribution solution for 400V applications. These applications include: 
•  Containerized data centers
•  Customers looking for global standard
•  Progressive data centers looking for cost reductions and efficiency gains
You can find 400V ePDUs featured in the Monitored, Switched and Managed sections of this catalog, as well as on 
eaton.com/epdu
.
400V ePDU part numbers (for reference)
Monitored
•  VPC2864-3861
•  VPC2864-3862
Switched
•  IPV70U1-EP1-09L
•  IPV70U2-EP1-09L
Managed 
•  eMA013
•  eMA014