Eaton 9130-1500RM 2U 103006449-6591 User Manual

Product codes
103006449-6591
Page of 4
SINGAPORE
Tel  : +65 6825 1684
Fax  : +65 6825 1689
EatonSEA@eaton.com
INDONESIA
Tel  : +62 21 2949 9000
Fax  : +62 21 2949 9001
MALAYSIA
Tel  : +603 7804 3618
Fax  : +603 7803 6193
THAILAND
Tel  : +66 2575 0530
Fax  : +66 2575 1579
VIETNAM
Hanoi
Tel  : +84 4 3936 5303
Fax  : +84 4 3936 5307
Ho Chi Minh
Tel  : +84 8 6255 6737
Fax  : +84 8 6255 6801
Eaton and Powerware are a trade names, 
trademarks and/or services mark of Eaton 
Corporation or its subsidiaries and affi liates.
® 2008 Eaton Corporation
All Rights Reserved 
Printed in Singapore
September 2012
Eaton 9130 UPS 
Product Focus
General
User interface
Graphical LCD with blue backlight and text in 
English, French, German, Russian and Spanish
LEDs
Four status-indicating LEDs
Topology
True online, double-conversion
Diagnostics
Full system self-test
UPS bypass
Automatic bypass
Dimensions
See models table
Rail kit
Included with all rackmount units
Electrical Input
Nominal voltage
120V, 220–240V
Voltage range
120V: 90–138 Vac
230V: 160–276 Vac
Power drawn from UPS 700:   3.0A @230V, 5.8A @120V
1000: 4.3A @230V, 8.3A @120V
1500: 6.5A @230V, 12.5A @120V
2000: 8.7A @230V, 16.6A @120V
3000: 13A @230V, 25A @ 120V
5000: 21.7A @230V
6000: 26A @230V  
Dedicated circuit     
breaker rating
UPS input rating
120V:
700–1500 VA: 15A
2000 VA: 20A
2500–3000 VA: 30A
230V:
700–2000 VA: 10A
3000 VA: 16A
5000 VA: 24A
6000 VA: 32A
Frequency
50/60 Hz
Frequency range
45–65 Hz
Electrical Output
Power factor
0.9
On utility voltage
±3% of nominal regulation
On battery voltage
±3% of nominal regulation
Efficiency
>95% in high-efficiency mode; >86% in online mode
Frequency regulation
±3% Hz online
Load crest factor
3 to 1
Battery
Battery type
VRLA 12V/9 Ah (both internal and external)
Battery runtime
See runtime table 
Battery replacement
Hot-swappable internal and external batteries
Start-on-battery
Allows start of UPS without utility input
Communications
Serial port
RS-232 standard, for interface to power management 
software
USB port
HID standard, for communicating with Windows XP/
Vista
Relay output
Common alarm standard
Communications slot
Optional communication slots
Optional communication 
cards
SNMP/Web card for direct control and monitoring 
in SNMP-based networks, monitoring of UPS status 
and meters through Web browser interface. 
Relay card for integration to industrial environment 
and building management systems, remote shut-
down for IBM AS/400 systems
Environmental
Safety markings
120V: UL, CUL, VCCI
230V: CE, GS
EMC markings
120V: FCC Class B, EN55022 Class B (1.5 kVA and
below); FCC Class A, EN55022 Class A (2.0 kVA
and above)
230V: CE (per IEC/EN62040-2: Emissions, Category
C1; Immunity, Category C2)
Audible noise
<50 dB
Ambient operating
temperature
0˚C (32˚F) to +40˚C (104˚F)
Storage temperature
-20˚C (-4˚F) to +40˚C (104˚F) with batteries and 
-25˚C (-13˚F) to +55˚C (131 ˚F) without batteries
Relative humidity
5–90% non-condensing
Heat dissipation for all voltages: 240V and 120V
In the interests of continual product improvement all specifications are subject to change without notice.
TECHNICAL SPECIFICATIONS
 9130 model 
Watts
 700 VA 
103
 1000 VA 
140
 1500 VA 
196
 2000 VA 
252
 3000 VA 
317
 5000 VA 
520
 6000 VA 
630