Altronix AL600ULXR Leaflet

Page of 2
Agency Approvals
Specifications
UL 294 
UL Listed for Access Control  
 
System Units.
UL 1481  UL Listed Standard for Safety for
 
Fire Protective Signaling Systems.
CUL Listed - CSA Standard C22.2 
No.205-M1983, Signal Equipment.
MEA -   NYC Department of 
 
Buildings Approved.
CSFM -  California State Fire 
 
Marshal Approved.
FM - Factory Mutual Approved.
Input:
•  Input 115VAC, 60Hz, 1.9 amp.
Output:
•  12VDC or 24VDC selectable output.
• 6 amp continuous supply current.
•  Filtered and electronically regulated output.
•  Short circuit and thermal overload protection.
Battery Backup:
•  Built-in charger for sealed lead acid or
 gel type batteries.
•  Automatic switch over to stand-by battery
 when AC fails.
•  Maximum charge current 0.7 amp.
Supervision:
•  AC fail supervision (form “C” contacts).
•  Low battery supervision (form “C” contacts).
•  Battery presence supervision (form “C” contacts).
Visual Indicators:
•  AC input and DC output LED indicators.
Electrical:
•  Operating temperature: 0º C to 49º C ambient.
•  27-55 BTU/Hr.
•  System AC input VA requirement: 218.5VA.
Mechanical:
•  Enclosure Dimensions (H x W x D approx.):
  13.5” (342.9mm) x 13” (330.2mm) x 3.25” (82.55mm)
 -  Accommodates up to two (2) 12VDC/7AH batteries.
•  Product weight (approx.): 7.6 lbs. (3.45 kg.).
•  Shipping weight (approx.): 8.5 lbs. (3.86 kg.).
AL600ULX is a power supply/charger which converts a 115VAC/60Hz input
into a single 12VDC or 24VDC non-power limited output.
AL600ULX
Power Supply/Charger
Rev. DSAL600ULX_04162012
Overview
AL600ULX