Altronix STRIKEIT1 Leaflet

Page of 2
• This dual channel unit is designed to provide 24VDC power for a maximum of 
two electrified panic devices with very high inrush requirements. Each channel 
has an adjustable relock delay input that will control a pair of doors 
simultaneously or independent control of two single doors. Unit has two sets of 
relays per channel which can be configured to trigger external relays, automatic 
door openers, ADA push plate switches etc. Unit can control automatic door 
operators where the doors are always locked or where the doors are unlocked 
during the business day. 
• Two (2) 24VDC individually controlled lock outputs
rated @ 16 amp for 300ms.
• One (1) 12VDC filtered regulated auxiliary output
rated @ 1.5 amp continuous supply current. 
(Not affected by FACP trigger)
• One (1) 24VDC filtered regulated auxiliary output
rated @ 1 amp continuous supply current. 
(Not affected by FACP trigger)
• Two (2) delayed follower form “C” relay outputs
rated @ 1 amp/28VDC. Delay time is 
selectable .5 seconds or 1 second.
Energized duration is 1 second.
• Two (2) follower form “C” relay outputs rated 
@ 1 amp/28VDC.
Relays energize while input is closed.
• Input 115VAC 50/60Hz, 1.9 amp.
• Two (2) N/O Trigger Inputs.
• Built-in charger for sealed lead acid or 
gel type batteries.
• Automatic switch over to stand-by battery 
when AC fails.
• Maximum charge current .3 amp.
• Green LED indicates input 115VAC present.
• Green LED indicates panic device status 
(short, open or triggered).
• Red LED indicates when FACP disconnect 
is triggered.
• Fire Alarm Disconnect:
- Normally Closed FACP trigger input.
- Programmable Fire Alarm Disconnect options:
a) Removes power to outputs and disables delayed 
follower relays.
b) Connects power to lock outputs and enables 
delayed follower relays.
• LK1 and LK2 adjust the panic device release time for 
the lock outputs from 300ms to 30 sec.
• Product weight: 13.7 lbs.
• Shipping weight: 14.7 lbs.
StrikeIt1 Panic Device Power Controller
Rev. DSStrikeIt - J26G
Overview
Specifications
Agency Approvals
MEA - NYC Department of Buildings Approved.
CSFM - California State Fire Marshal Approved.
UL Listed for Access Control Systems Units (UL 294).
CUL Listed - CSA Standard C22.2 No.205-M1983, Signal Equipment.