Altronix MAXIMAL3R Leaflet

Page of 2
 Altronix new Maximal3R rack mount access power controller distributes and switches power to access control
systems and accessories. It converts a 115VAC 50/60Hz input into sixteen (16) independently controlled 12VDC
or 24VDC fuse protected outputs. Outputs are activated by an normally open (NO) or normally closed (NC)
dry trigger input from an Access Control System, Card Reader, Keypad,
Push Button, PIR, etc. This unit will route power to a variety of 
access control hardware devices including: Mag Locks, Electric 
Strikes, Magnetic Door Holders, etc. Outputs will operate in both 
Fail-Safe and/or Fail-Secure modes. The FACP Interface enables 
Emergency Egress, Alarm Monitoring, or may be used to
trigger other auxiliary devices. The fire alarm disconnect
feature is individually selectable for any or all of the outputs. 
Input:
•  115VAC 60Hz., 1.9 amp.
•  Normally closed [NC] or normally open [NO]
  dry contact inputs (switch selectable).
Outputs:
•  12VDC or 24VDC @ 6 amp total output current.
•  Sixteen (16) fuse protected outputs.
•  Maximum current per ACM8R-M output is 2.5 amp.
•  Individually selectable Mag Lock/Strike (Fail-Safe,
  Fail-Secure) solid state fuse protected outputs.
•  Thermal and short circuit protection with auto reset.
Fire Alarm Interface:
•  Latching or Non-Latching fire alarm reset switch
  individually selectable for each output.
•  Remote reset capability for latching Fire Alarm
  Interface mode.
•  Fire Alarm disconnect input options:
 a)  Normally open [NO] or normally closed [NC]
    dry contact input.
  b)  Polarity reversal input from FACP signaling 
    circuit.
Visual Indicators:
•  Individual Output Status LEDs located on the
  front panel.
Battery Backup:
•  Built-in charger for sealed lead acid or gel type
  batteries (if batteries are required install 
  separate enclosure). 
•  Maximum charge current 0.7 amp.
•  Automatic switch over to stand-by battery
  when AC fails.
•  Zero voltage drop when unit switches over to battery
  backup (AC failure condition).
Supervision:
•  AC fail supervision (form “C” contact).
•  Low battery and battery presence supervision
 (form “C” contact).
Additional Features:
•  Removable terminal blocks with locking screw flange.
•  3-wire line cord.
•  Illuminated master power disconnect circuit breaker
  with manual reset.
Rack Dimensions:
3.25”H x 19.125”W x 8.5”D
Shipping Weight (approximate):
-  Maximal3R: 12.7 lbs.
Maximal3R
Rack Mount Access Power Controller
Rev. DSMaximal3R - A19K
Overview
Specifications