Altronix ACM4CBE Leaflet

Page of 2
ACM4, ACM4E, ACM4CB and ACM4CBE
Multi-Output Access Power Controllers
Rev. DSACM4 - D07H
•  These units convert one (1) 12 to 24 volt AC or DC input into four (4)
 independently controlled fused or PTC protected outputs. These power
 outputs can be converted to dry form “C” contacts (ACM4 & ACM4E only).
 Outputs are activated by an open collector sink or normally open (NO) dry
 trigger input from an Access Control System, Card Reader, Keypad, Push
 Button, PIR, etc. The units will route power to a variety of access control
 hardware devices including Mag Locks, Electric Strikes, Magnetic Door
 Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure
 modes. Units are designed to be powered by one common power source
 which will provide power for both the board operation and locking devices,
 or two (2) totally independent power sources, one (1) providing power for
 board operation and the other for lock / accessory power. The FACP Inter
 face enables Emergency Egress, Alarm Monitoring, or may be used to  
 trigger other auxiliary devices. The fire alarm disconnect feature is
 individually selectable for any or all of the four (4) outputs.
Overview
ACM4
•  Access Power Controller w/fuse
 protected outputs.
ACM4CB
•  Access Power Controller w/PTC
 protected outputs.
ACM4E
•  ACM4 w/enclosure.
ACM4CBE
•  ACM4CB w/enclosure.
•  12 to 24 volt AC or DC operation
 (setting not required), (.4 amp @ 12volt,
 .2 amp @ 24 volt current consumption with all
 relays energized).
•  Power supply input options:
 a) One (1) common power input
   (board and lock power).
 b) Two (2) isolated power inputs (one (1) for
   board power and one (1) for lock/accessory power).
•  Four (4) Access Control System trigger inputs:
 a)  Four (4) normally open (NO) inputs.
 b) Four (4) open collector sink inputs.
 c)  Any combination of the above.
•  Four (4) independently controlled outputs:
 a)  Four (4) Fail-Safe and/or Fail-Secure
   power outputs.
 b) Four (4) dry form “C” 5 amp rated relay outputs
   (ACM4/ACM4E only).
 c)  Any combination of the above
   (ACM4/ACM4E only).
•  Four (4) auxiliary power outputs (unswitched).
•  Output ratings:
 - Fuses are rated 3 amp each (ACM4/ACM4E).
 - PTCs are rated 2.5 amp each (ACM4CB/ACM4CBE).
•  Main fuse is rated at 10 amp.
 Note: Total output current is determined by the
 power supply, not to exceed a maximum
 of 10 amp total.
•  Red LEDs indicate outputs are triggered
 (relays energized).
•  Fire Alarm disconnect (latching or non-latching) is
 individually selectable for any or all of the
 four (4) outputs.
 Fire Alarm disconnect input options:
 a)  Normally open (NO) or normally closed (NC)
   dry contact input.
 b) Polarity reversal input from FACP
   signaling circuit.
•  FACP output relay (form “C” contact rated @ 1 amp
 28VDC not evaluated by UL).
•  Green LED indicates when FACP disconnect
 is triggered.
•  Removable terminal blocks facilitate ease
 of installation.
•  Product weight (approximate):
 -  ACM4E: 6.6 lbs.
 -  ACM4CBE: 6.7 lbs.
•  Shipping weight (approximate):
 -  ACM4E: 7.5 lbs.
 -  ACM4CBE: 7.6 lbs.
ACM4
ACM4E
Specifications