Altronix AL300ULMR Leaflet

Page of 2
• 12VDC or 24VDC selectable output. 
• 2.5 amp supply current.
• Five (5) individual Class 2 Rated power 
limited outputs rated @ 2.5 amp.
• Current limit is 12VDC or 24VDC @ 2 amp  
per output.
• Input 115VAC / 60Hz, 1.45 amp.
• Input fuse rated @ 3.5 amp/250V.
• Fire Alarm Panel or Access Control System trigger 
inputs. N.O. or N.C. supervised trigger input and 
polarity reversal trigger input.
• Output relay energizes when unit is triggered 
(form “C” contact rated 1 amp @ 28VDC).
• Power fail supervision relay (form “C” contact rated 
1 amp @ 28VDC).
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
• Built-in charger for sealed lead acid 
or gel type batteries.
• Maximum charge current .7 amp.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
• AC fail supervision (form "C" contacts). 
• Low battery supervision (form "C" contacts). 
• Battery presence supervision (form “C” contacts).
• AC input and DC output LED indicators
(power supply board).
• Red LEDs indicate condition of power outputs
(multi-output board).
• Power & input trigger LEDs (multi-output board).
• Enclosure:
- Combination knockouts re 1/2” and 3/4”
- Accommodates up to two (2) 12VDC/7AH 
batteries.
• Product weight: 
- AL300ULM: 7.6 lbs.
- AL300ULMR: 8.1 lbs.
• Shipping weight: 
- AL300ULM: 8.6 lbs.
- AL300ULMR: 9.1 lbs.
AL300ULM
• Grey enclosure. 
AL300ULMR
• Red enclosure. 
• These multi-output access control power supply/chargers are specifically 
designed for use with access control systems and accessories. These units 
convert a 115VAC / 60Hz input into five (5) individually protected 
Class 2 Rated power limited 12VDC or 24VDC outputs (see specifications). 
Each output will route power to a variety of access control hardware devices 
including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. 
These outputs will operate in both Fail-Safe and Fail-Secure modes. 
Controlled trigger input is achieved through normally open (N.O.) or 
normally closed (N.C.) supervised input or the polarity reversal from an 
FACP (Fire Alarm Control Panel). A form “C” dry output relay enables 
HVAC Shutdown, Elevator Recall or may be used to trigger auxiliary devices.
AL300ULM(R) Multi-Output Access Control 
Power Supply/Charger
Rev. DSAL300ULM - L05F
Overview
Specifications
UL Listed for Access Control Systems Units 
(UL 294).
UL Listed Standard for Power Supplies for Use
with Burglar-Alarm System Units (UL 603).
UL Listed Hospital Signaling and Nurse Call
Equipment (UL 1069).
UL Listed Standard for Safety for Fire
Protective Signaling Systems (UL 1481).
CUL Listed - CSA Standard C22.2 
No.205-M1983 Signal Equipment.
Agency Approvals
MEA - NYC Department of 
Buildings Approved.
CSFM - California State Fire 
Marshal Approved.