Altronix MAXIMAL77 Leaflet

Page of 2
Maximal77
Access Power Controller
Rev. DSMaximal77 - F27K
This unit distributes and switches power to access control systems and
accessories. They convert a 115VAC 60Hz input into sixteen (16) independently
controlled 24VDC fuse protected outputs. These Fail-Safe/Fail-Secure power out-
puts may be converted to dry form “C” contacts. The outputs are activated by an 
open collector sink or normally open (NO) dry trigger input from an Access Control 
System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of 
access control hardware devices including: Mag Locks, Electric Strikes, Magnetic 
Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm
Monitoring, or may be used to trigger other auxiliary devices. The fire alarm
disconnect feature is individually selectable for any or all of the sixteen (16) outputs. 
All interconnecting equipment must be UL Listed.
Overview
•  24VDC outputs.
•  Maximum output current: 24VDC @ 19.4 amp.
 
Options 
P/S 1 
P/S 2
  A 
24VDC @ 9.7 amp 
24VDC @ 9.7 amp
•  115VAC 60Hz, 12.5 amp input.
•  Input fuse rated @ 10 amp/250V.
•  Power supply input options: 
  a) Two (2) common power input for either ACM8
    and lock power (factory installed).
  b) Two (2) isolated power inputs (external power
    supply is required), (current is determined by the  
    power supply connected, not to exceed a 
    maximum of 10 amp total).
•  Sixteen (16) Access Control System trigger inputs.
  Input options:
  a) Sixteen (16) normally open (NO) inputs.
  b) Sixteen (16) open collector inputs.
  c) Any combination of the above.
•  Sixteen (16) independently controlled outputs.
  Output options:
  a) Sixteen (16) Fail-Safe and/or Fail-Secure
    power outputs.
  b) Sixteen (16) form “C” 5 amp rated relay outputs.
  c) Any combination of the above. 
•  Sixteen (16) auxiliary power outputs (unswitched)  
  (outputs are rated 2.5 amp).
•  ACM8 boards main fuse is rated at 10 amp.
  Output fuses are rated @ 3.5 amp.
•  Red LEDs indicate outputs are triggered
  (relays energized).
•  Fire Alarm disconnect (latching or non-latching) is  
  individually selectable for any or all of the
  sixteen (16) outputs.
•  Fire Alarm disconnect input options:
  a) Normally open (NO) or normally closed (NC) dry  
    contact input.
  b) Polarity reversal input from FACP signaling circuit.
•  Alarm output relay indicates that FACP input is
  triggered (form “C” contact rated @ 1 amp 28VDC).
•  Green LED indicates FACP disconnect is triggered.
•  Filtered and electronically regulated outputs (built-in  
  power supply).
•  Built-in charger for sealed lead acid or gel type
  batteries.
•  Maximum  charge current 3.6 amp.
•  Automatic switch over to stand-by battery when
  AC fails.
•  Zero voltage drop when unit switches over to battery  
  backup (AC failure condition).
•  Thermal and short circuit protection with auto reset. 
•  AC input and DC output LED indicators.
•  AC fail supervision (form “C” contact). 
•  Low battery and battery presence supervision
  (form “C” contact).
•  Enclosure accommodates up to four (4)
  12AH batteries.
Maximal
77 weights
 (approximate):
•  Product weight: 41.25 lbs. 
•  Shipping weight: 45.25 lbs.
Maximal77
Specifications