Eaton HotSwap MBP, 4x DIN 68431 Leaflet

Product codes
68431
Page of 2
In the interests of continuous product improvement all specifications are subject to change without notice.  
© 2009 Eaton Corporation, All Rights Reserved, April 2009.
2
Eaton FlexPDU
Eaton HotSwap MBP 
Part Numbers
Eaton FlexPDU
Eaton HotSwap MBP
Eaton EX RT PDU
FR
FlexPDU 8 FR: 68 435
HotSwap MBP 4 FR: 68 430
/
DIN
FlexPDU 8 DIN: 68 436
HotSwap MBP 4 DIN: 68 431
/
BS
FlexPDU 6 BS: 68 437
HotSwap MBP 3 BS: 68 432
/
IEC
FlexPDU 12 IEC: 68 438
HotSwap MBP 6 IEC: 68 433
Eaton EX RT PDU: 66 857
HW (Hard-Wired)
/
HotSwap MBP HW: 68 434
/
10A French/Schuko cable kit for HotSwap MBP
/
68 439
/
10A British cable kit for HotSwap MBP
/
68 440
/
Cables
Typical applications
Part numbers
2 IEC 10A (IEC C13 - IEC C14) cable kit
Extra output cables for UPSs
66 395
1 IEC 16A (IEC C20 - IEC C19) cable
For connecting to the IEC 16A output of a UPS
66 396
2 16A FR/Schuko cable kit
Connecting Eaton STS 16 to wall sockets
66 397
1 IEC 10A/16A (IEC C14 - IEC C19) cable
connecting Eaton STS to IEC 10A outlets
66 029
1 BS power cable
BS input power cable for 2.2 to 3 kVA UPSs
66 236
1 Swiss power cable
Swiss input power cable for 2.2 to 3 kVA UPSs
66 243
 Flexible system for 19” rack-mounting or on Eaton RT UPSs
 French/Schuko/British/IEC 10A sockets
 IEC 16A output for cascading
  IEC 16A input socket
 Retaining clip
 Flexible system for 19” rack-mounting or on Eaton RT UPSs
 French/Schuko/British/IEC 10A sockets
 IEC 16A output for cascading
  IEC 16A input socket
 Retaining clip
 Rotary bypass switch
  Colour coded input and output sockets for connecting the UPS 
NB: hard-wired version available
Eaton FlexPDU
Eaton HotSwap MBP
FR
DIN/
Schuko
BS
IEC C13 
10 A
IEC C19 
16 A
IEC C14 
10 A
IEC C20 
16 A
Eaton FlexPDU
Eaton HotSwap MBP
Eaton EX RT PDU
Current rating
16 A
16 A
52 A
Voltage rating
220-230-240-250 V
Installation
Format
1U (except BS) 19” rack-mounting  
with multi-position mountings
>1U 19” rack-mounting 
with multi-position mountings
2U 19” rack
Installation
19” rack horizontal or vertical mounting or on Eaton RT UPSs
19” rack or wall mounting
Dimensions H x W x D
44 x 483 x 80 mm (BS: 52 x 483 x 120 mm)
52 x 483 x 120 mm
89 x 483 x 90 mm
Connection
Inputs
1 IEC C20 (16A) connector and 2 cables 
(1 IEC 16A - 16A cable and 1 IEC 10A - 16A cable) 
for connection to any UPS
FR / DIN / BS / IEC models: 1 IEC C20 (16A) 
connector and 1 IEC 16A - 16A cable 
(1)
 
HW (Hard-Wired): terminal block
Pre-wired 0.5 m cable for connection
Outputs
FR
8 French sockets + 1 IEC 16A socket
4 French sockets + 1 IEC 16A socket 
/
DIN
8 Schuko sockets + 1 IEC 16A socket
4 Schuko sockets + 1 IEC 16A socket
/
BS
6 British sockets + 1 IEC 16A socket  
(with 2 circuit breakers)
3 British sockets + 1 IEC 16A socket  
(with 1 circuit breaker)
/
IEC
12 IEC 10A sockets + 1 IEC 16A socket 
(with 2 circuit breakers)
6 IEC sockets + 1 IEC 16A sockets  
(with 1 circuit breaker)
8 IEC 10A sockets + 4 IEC 16A sockets 
(with 4 circuit breakers)
HW
NA
Terminal block
/
Cascading
Yes, IEC 16A output socket (except HW)
Retaining clips
Retaining clips on the IEC input and output sockets
Operating conditions, standards and approvals
Operating temperature
0°C to 45°C continuous
Performance - Safety - EMC FR models: IEC 60 884-1 - DIN models: DIN 49 440-1, DIN 49 440-5, DIN 49 440-6 - BS models: BS 1363 
IEC models: IEC 60 320-1, EN 60 320-1 - HW models: IEC 60 950, EN 50 091
IEC/EN 60 320-1
Approvals
CE
1: Use cable kits P/N 66 439 (French/Schuko) or 66 440 (British) for connecting a low power UPS <2.2 kVA (with IEC 10A outputs) - see below.
Technical Specifications