Liebert MPXIPC-NXH30XXX User Manual

Page of 40
Liebert
®
 MPX
 System Modules
7
Figure 4
MPX PEM
 (Power Entry Module) features
2.2.1 MPX
 IPC
—Input Power Cord/Communication (North American Models Only)
The MPX IPC is a detachable input power cord that permits changing the input power source for 
Variable-Capacity versions of the MPX PEM
. A variety of single- and three-phase NEMA and IEC 
plug types are available. The MPX IPC is not required for the Fixed-Capacity MPX PEM.
Figure 5
MPX IPC connector
!
WARNING
Risk of arc flash and electric shock. Can cause equipment damage, injury or death.
Do not connect the MPX IPC to power until the MPX PEM is attached to the MPX PRC
 and 
the MPX IPC is attached to the MPX PEM. If the MPX PEM is not attached to the MPX PRC, 
conductors with hazardous voltage will be exposed when power is connected.
Liebert RPC 
Installed in Slot
Quick-Connect 
Power Couplings
Integral 
Connector
Torx Screw
Alarm 
Silence/Test 
Button
Phase Power 
Indicators
Hard-Wired
Power Input
Cable
Integral 
Connector
Torx Screw
Liebert RPC
 
Reset Access 
Hole
Quick-Connect
Power Couplings
Snap Locks prevent
accidental disconnection 
from the MPX PEM (Power 
Entry Module)