Liebert MPXIPC-NXH30XXX User Manual

Page of 40
Specifications
31
7.5
Agency Approvals
120V and 240V Single-Phase and 120/208-240V Three-Phase North American Units
• UL60950-1: Information Technology Equipment - Safety, Part 1 General Requirements
• CSA C22.2 No. 60950-1: Information Technology Equipment - Safety, Part 1 General 
Requirements
• FCC, Title 47, Part 15 Subpart B for Class B operation as defined by ANSI Standard C63.4.
• ISTA Procedure 1A and 2A
• RoHS Compliant
230V Single-Phase and 400V Three-Phase European Units
• CE Markings GS mark (safety tested) according to DIN EN 60950-1 (VBE 0805-1) 2006/95/EC 
and EMC Directive (EMD) 2004/108/EC according to the Low-Voltage Directive (LVD)
• CE Compliant according to:
• Low-Voltage Directive 2006/95/EC
• Electromagnetic - Compatibility Directive 2004/108/EC (EMD)
• RoHS Directive 2002/95/EC
• WEE Directive 2002/96/EC
• ISTA Procedure 1 A and 2A
• ROHS and WEEE Compliant, Basic Test for Purchased Products according to International Safe 
Transit Association
Table 5
Electrical and environmental specifications
Power Consumption, W
22 maximum per fully configured 42U model (RPC, BDM, PEM, 6xBRM-R)
3 per RPC; 0.4 per module + 0.4 per open control (energized condition)
Maximum Ratings
240/415V 50/60Hz 63A
Insulation
Class I, Basic Earthed SELV
Electric Strength, VDC
2200
Overcurrent Protection
UL489 Overcurrent Circuit Breaker per Branch, 20A, 5000A A.I.C
Operating Temperature, °C (°F)
5-55 (41-131)
Humidity, %
10-95, non-condensing
Altitude, m (ft.)
2000 (6560)
Table 6
Metering performance
Accuracy, %
Volts, V
±1
Current, A (per %rated value)
±2 from 1% to <10%
±1 from 10% to 125%
Measurement, Resolution
Power Entry Module (PEM)
Branch Receptacle Module (BRM
)
Branch
Receptacle
Phase Voltage, 0.1V
Line Voltage, 0.1V
Line Current, 0.01A
Neutral Current, 0.01A
(3-phase only)
Total Real Power, 0.1W
Total Real Energy, 0.1kW-hr
Real Power, 0.1W
Apparent Power, 0.1VA
Real Energy, 0.1kW-hr
Power Factor, 0.01
Crest Factor, 0.01
Frequency, 0.1Hz