Eaton 9135 UPS PPDM EPPDMG6000-3U-4 User Manual

Product codes
EPPDMG6000-3U-4
Page of 57
INSTALLATION
EATON Two-in-One PPDM (5000/6000 VA) User's Guide  
S
  164201820 Rev 1  www.eaton.com/powerquality
19
Hardwired PPDM Installation
W
 
A
 
R
 
N
 
I
 
N
 
G
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
C
 
A
 
U
 
T
 
I
 
O
 
N
S
For PPDM models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S
For PPDM models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
NOTE  Do not make unauthorized changes to the UPS or PPDM; otherwise, damage may
occur to your equipment and void your warranty.
The hardwired PPDM models require a dedicated branch circuit that
meets the following requirements:
S
40A minimum circuit with short circuit and overcurrent protection
S
200–240 Vac
S
Single phase
S
50/60 Hz
S
The breaker must be wallmounted and be readily accessible to the
operator
S
Flexible metal conduit (recommended for ease of service and
maintenance)