Toshiba VF-AS1 User Manual

Page of 326
!
  E6581301!
M-2 
13
(Continued) 
Error 
code
Description 
Possible causes 
Remedies 
QN Inverter 
overload 
•Rapid acceleration is operated.
•The DC braking amount is too 
large. 
•The V/f setting is improper. 
•A restart signal is input to the 
rotating motor after a momentary 
stop, etc. 
•The load is too large.
•Increase the acceleration time CEE.
•Reduce the DC braking amount H and the 
DC braking time H. 
•Check the V/f parameter setting. 
•Use WX (Auto-restart) and WXE (Regenerative 
power ride-though control). 
•Use an inverter with a larger rating.
QN Motor overload
•The V/f parameter is improperly 
set.
•The motor is locked up. 
•Low-speed operation is performed 
continuously. 
•An excessive load is applied to the 
motor during operation. 
•Check the V/f parameter setting.
•Check the load (operated machine). 
•Check the QNO setting and adjust H
according to the sustainable overload in the motor 
low-speed range. 
•Reduce the DC braking amount H and the 
DC braking time H. 
QNT
Dynamic 
braking resistor 
overload 
•Rapid deceleration is operated.
•Dynamic braking is too large. 
•Increase the deceleration time FGE.
•Increase the capacity of dynamic braking resistor 
(wattage) and adjust PBR capacity parameter 
RDER.
QR
Overvoltage 
during 
acceleration 
•The input voltage fluctuates abnormally.
(1)The power supply has a capacity 
of 500kVA or more. 
(2)A power factor improvement 
capacitor is opened and closed.
(3)A system using a thyrister is 
connected to the same power 
distribution line. 
•A restart signal is input to the 
rotating motor after a momentary 
stop, etc.
•Insert a suitable input reactor.
•Use WX (Auto-restart) and WXE (Regenerative 
power ride-though control). 
QR
Overvoltage 
during 
deceleration 
•The deceleration time FGE is too 
short (regenerative energy is too 
large).
•The dynamic braking resistor has 
a considerably large resistance. 
•RD (Dynamic braking resistor) is OFF.
Overvoltage limit operation H
is OFF.
•The input voltage fluctuates abnormally.
(1)The power supply has a capacity 
of 500kVA or more. 
(2)A power factor improvement 
capacitor is opened and closed.
(3)A system using a thyrister is 
connected to the same power 
distribution line.
•Increase the deceleration time FGE.
•Install a dynamic braking resistor. 
•Decrease dynamic braking resistance. (Also reset 
the RDT.) 
•Set dynamic braking mode parameter RD
properly. 
•Set overvoltage limit operation H properly. 
•Insert a suitable input reactor. 
QR
Overvoltage 
during fixed 
speed operation
•The input voltage fluctuates abnormally.
(1)The power supply has a capacity 
of 500kVA or more. 
(2)A power factor improvement 
capacitor is opened and closed. 
(3)A system using a thyrister is connected 
to the same power distribution line. 
•The motor is in a regenerative 
state because the load causes the 
motor to run at a frequency higher 
than the inverter output frequency.
•The undervoltage detection level 
H is too low. 
•Insert a suitable input reactor.
•Install a dynamic braking resistor. 
•Check the undervoltage detection level H.
*QV
Overtorque 
•Overtorque reaches to a detection 
level during operation. 
•Stall prevention operation was 
performed continuously for a 
length of time longer than that set 
with H.
•Check system error.
•Check whether the motor is overloaded or the 
brake is engaged. 
*WE
Low current   
•The output current decreased to a 
low-current detection level during 
operation.
•Check the suitable detection level for the system 
(H). 
•Contact your Toshiba distributor if the setting is correct.
*WR
Voltage drop in 
main circuit 
•The input voltage (in the main 
circuit) is too low. 
•Momentary power failure occurs 
because undervoltage continues 
longer than undervoltage detection 
time H. 
•Check the input voltage.
•To cope with a momentary stop due to 
undervoltage, enable WXE (Regenerative power 
ride-through control), WX (auto-restart control), 
and H (Undervoltage detection time). 
  *Presence or absence of parameter trip can be selected. 