Tripp Lite BCPRO850 User Manual

Page of 4
completely locked computers by automatically switching UPS power off and back on again 
PowerAlert UPS monitoring and shutdown software available via free download from http://www.tripplite.com 
Two front panel switches support power off/on control, alarm cancel and UPS self test functions
Built-in audible alarm and 5 front panel LEDs indicate line power, battery power, battery low/replace and overload status
850VA power handling ability supports a variety of computer, internetworking, telecom and overload status
Supports hot swappable user battery replacement via built-in access panel
Compatible with 120V/60Hz applications 
UL1778 listed (USA), cUL (Canada), NOM (Mexico), FCC Class B
2 year manufacturers warranty
$200,000 
connected equipment insurance
 (USA & Canada only)
Specifications
OUTPUT
Frequency
compatibility
60 Hz
Output VA
850
Output watts
600
Output nominal
voltage
120V AC
Output voltage
regulation
BATTERY MODE: PWM sine wave output 115V +/-5%
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% 
BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type
6 NEMA 5-15R
INPUT
UPS Input cord
length (ft.)
6 ft., 16 gauge
Recommended
Electrical Service
15A 120V
Maximum Input Amps
(A)
5.8A / 650 watts
Input connection type
NEMA 5-15P
Voltage compatibility
(VAC)
120
BATTERY
DC system voltage
(VDC)
18
Battery Access
Battery access door allows user replacement of UPS batteries
Full load runtime
9 minutes (850VA)
Half load runtime
26 minutes (425VA)
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate
2-4 hours to 90%
LEDS ALARMS & SWITCHES
Alarms
Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.