Tripp Lite SU3000RTXL3UHV User Manual

Page of 5
Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems
Accepts input voltages between 160 and 275 (130 to 275 at loads under 70%), regulating output to selectable 200/208/220/230/240V +/-2%
3000VA/2400 watt power capacity with 8 total outlets (6 NEMA6-15/20R & 2 NEMAL6-20R) 
Standard internal battery set provides 14 minutes runtime at half load
Expandable runtime with multiple external battery packs (part# BP72V15-2U limit 1/BP72V28-3U multi-pack compatible)
Innovative design makes unit adaptable for rackmount, tower, or stacking applications 
Uses only 3 rack spaces (3U) in standard 19 inch rack
DB9 serial port for network interface; SNMP compatible
Slot for optional SNMP/web card (part# SNMPWEBCARD) 
PowerAlert unattended shutdown software and 6 ft. network cable included 
Compatible with Tripp Lite's Watchdog Service Monitoring/Reboot Software
Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or
suffers an internal failure that requires service
Diagnostic LEDs 
Battery replacement door 
Mounting hardware included for 4 post rack enclosures, 2 post telecom rack compatible with separate purchase 2POSTRMKITWM
accessory
$250,000 Ultimate Lifetime 
connected equipment insurance
2 year manufacturer's product warranty 
Specifications
SYSTEM OVERVIEW
Voltage
compatibility
208V AC
Frequency
compatibility
50/60 Hz compatible
OUTPUT
Output VA
3000
Output watts
2400
Output nominal
voltage
208V AC (200/220/230/240V)
Output voltage
regulation
Maintains full-time sine wave output within 2% of selected nominal voltage, less than 5% total harmonic distortion
Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity /
type
6 NEMA 6-15/20R, 2 NEMA L6-20R
Customized load
management
receptacles
2 individually controllable load banks support load shedding and remote reboot on demand of locked network devices.
Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers
and other critical devices. (Bank A consists of 4 outlets / Bank B consists of 2 outlets)
Overload protection
Via 25A input breaker
INPUT
Maximum input
amps
14.9 / 14.3 / 13.1 / 12.6 / 12.1 Amps (depending on voltage) / 2844 watts
Input connection
type
NEMA L6-20P
Input cord length
10 ft. 14 gauge
Recommended
Electrical Service
15A 200-240V
BATTERY
Full load runtime
Internal batteries — 5 min. (3000VA)
Half load runtime
Internal batteries — 14 min. (1500VA)