Eaton 9135 UPS PPDM EPPDMG6000-3U-1 User Manual

Product codes
EPPDMG6000-3U-1
Page of 57
EATON Two-in-One PPDM (5000/6000 VA) User's Guide  
S
  164201820 Rev 1  www.eaton.com/powerquality
37
Chapter 4
Specifications
 Table 4. Model Specifications
Model
Input
Voltage
Input
Current
Output Voltage
1
Output
Current
Output Receptacles
EPPDMG6000-3U-HW
208/240V
30A
115/120V
41A/208V
45A/240V
Hardwired
208/240V
30A
EPPDMG-6000-3U-HW
EU
230/240V
30A
115/120/230/240V
30A
Hardwired
EPPDMG-6000-3U-1
(L6-30)
208/240V
24A
115/120/208/240V
30A
(1) L6-30R, (8) 5-15R
EPPDMG-6000-3U-2
(L6-20)
208/240V
24A
115/120V
20A
(1) L6-20R, (8) 5-15R
208/240V
30A
EPPDMG-6000-3U-3
(L5-30)
208/240V
24A
115/120V
41A/208V
45A/240V
(1) L5-30R, (8) 5-15R
EPPDMG-6000-3U-4
(L14-30)
208/240V
24A
115/120V
41A/208V
45A/240V
(1) L14-30R, (8) 5-15R
208/240V
30A
EPPDMG-6000-3U-5
(L6-30&L14-30)
208/240V
24A
115/120V
41A/208V
45A/240V
(1) L6-30R, (1) L14-30R,
(4) 5-15R
208/240V
30A
EPPDMG-6000-3U-6
(L6-30)
208/240V
24A
115/120/208/240V
30A
(2) L6-30R, (4) 5-20R
EPPDMG-6000-3U-2
(L6-20)
208/240V
24A
115/120V
20A
(2) L6-20R, (4) 5-20R
208/240V
30A
1
 Output voltage varies ±5% based on the attached load.