SPECIFICATION
DR-4505
DR-4512
DR-4515
DR-4524
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
5V
12V
15V
24V
5A
3.5A
2.8A
2A
0 ~ 5A
0 ~3. 5A
0 ~ 2.8A
0 ~ 2A
25W
42W
42W
48W
100mVp-p
200mVp-p
240mVp-p
13.5 ~ 16.5V
480mVp-p
21.6 ~ 26.4V
2.0%
1.0%
1.0%
1.0%
10.8 ~ 13.2V
4.75 ~ 5.5V
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
1.0%
800ms, 60ms/230VAC at full load
60ms/230VAC at full load
85 ~ 264VAC
120 ~ 370VDC
47 ~ 63Hz
72%
77%
77%
80%
1.5A/115VAC
0.75A/230VAC
COLD START 28A/115VAC
56A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V
Protection type : Shut off o/p voltage, clamping by zener diode
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
Tj 135
typically (U1) detect on heat sink of power transistor
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +50
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/
(0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
364.6K hrs min.
MIL-HDBK-217F (25
)
93*78*67mm (L*W*H)
0.31Kg; 48pcs/17.5Kg/1.3CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25
of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-45-SPEC 2011-06-07
UL508, TUV EN60950-1 approved
Compliance to EN55011,EN55022 (CISPR22)
,
Class B EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
45W Single Output Industrial DIN Rail Power Supply
D R - 4 5
s e r i e s
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 100KHz
3 years warranty
Features :
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
/ 70% RH
EMC IMMUNITY
EMC EMISSION