Eaton IPV3742-3883 Catalog

Page of 48
REMOTE START REQUIRES (2) CONDITIONS:
 
1.  The on/off/remote switch must be in the remote position.
 
2.  
A maintained closure between pins 1 & 3 turns the  
unit on.
REMOTE POWER OFF REQUIRES (1) CONDITION:
  
Opening the maintained connection between pins 1 & 3 turns 
off the switched outlets.
REMOTE EPO REQUIRES (1) CONDITION:
  
A maintained contact between pins 2 & 3 turns off the 
switched outlets regardless of the position of the on/off/
remote switch.
SEQUENCED REMOTE:
Connect pins 1, 2 & 3 of the sequence port to pins 1, 2 & 3 on  
any remote port of the slave unit. (Do not connect to another 
sequence port!) 
The sequence port of the master unit activates four seconds 
after the final set of outlets turn on. Additional units may be daisy 
chained in this fashion.
CAUTION!
THIS TYPE OF REMOTE IS NOT TO BE SUBSTITUTED 
FOR A SAFETY INTERLOCK!
EPO is normally open, so removing the EPO connection 
will not shut down the power to the unit.
Latching remote LT control interface
REMOTE START REQUIRES (2) CONDITIONS:
 
1.  A maintained contact between pins 2 & 3.
 
2.  A momentary contact between pins 1 & 3.
REMOTE POWER OFF OR EPO REQUIRES (1) CONDITION:
 
 Opening the maintained connection between pins 2 & 3. 
Additional EPO or stop buttons can be connected in series 
between pins 2 & 3. 
  
This turns off the switched outlets regardless of the remote 
switch position.
SEQUENCE REMOTE:
Connect pins 1 & 2 of the sequence port to any remote port on 
another -LT unit. The sequence port activates four seconds 
after the final set of outlets turn on. (Do not connect to another 
sequence port!)
NOTE:  LT units are designed for remote operation only. Even when 
the REMOTE/OFF/LOCAL switch is set to LOCAL, the unit still 
requires a power request from the remote ports to turn the 
unit on.
REMOTE OPERATION: Most Eaton units have more than one remote connector. Unless labeled as SEQUENCE they are wired in parallel. Connection 
to only one remote connector is required. It is recommended that an Eaton control panel be ordered for use with your PDU. Connectors are provided 
for those who wish to wire their own switches or control panels. We recommend using 14 AWG wire and not exceeding 50 feet for any remote cable. 
Mating control panels can be seen on our website at eaton.com/epdu.
If additional remote connectors are needed: The female AMP connectors used in our Power Controllers are: three pin - part number 1-480304-0 and 
four pin part number 1-480425-0, and are used with AMP Socket Terminals, part number 60619-1. The mating male AMP connector is: three pin -  
part number 1-480305-0, and four pin - part number 1-480426-0 and are used with AMP male contacts part number 60620-1.
Sample remote circuits
Standard remote control interface
eaton.com/epdu 1.800.356.5794
39
Indus
trial ePDUs